11 auxiliary parameters, 1 slip compensation (pr. 95 , pr. 96 , pr. 97 ) – MITSUBISHI ELECTRIC FR-S520E User Manual
Page 134
124
Auxiliary parameters
2.11 Auxiliary parameters
2.11.1 Slip compensation (Pr. 95
, Pr. 96
, Pr. 97
)
*When this value is made smaller, response will be faster.
However, as load inertia is greater, a regenerative overvoltage (OVT) error is
more liable to occur.
The inverter output current may be used to assume motor slip to keep the motor
speed constant.
Parameter
Name
Factory
Setting
Setting Range
Remarks
95
Rated motor slip
- - -
0 to 50%, - - -
Setting is enabled
when Pr. 30 = "1"
96
Slip compensation time
constant
0.5s
0.01 to 10s
97
Constant-output region slip
compensation selection
- - -
0, - - -
Rated slip =
Synchronous speed at base frequency - rated speed
×100[%]
Synchronous speed at base frequency
Parameter
Setting
Function
95
0.01 to 50%
Used to set the rated motor slip.
0, - - -
Slip compensation is not made.
96
0.01 to 10s
Used to set the slip compensation response time. (*)
97
0
Slip compensation is not made in the constant output range
(frequency range above the frequency set in Pr. 3).
- - -
Slip compensation is made in the constant output range.
REMARKS
When making slip compensation at 60Hz, set the maximum frequency (Pr. 1) to slightly higher
than 60Hz.
In the factory setting status, it is clamped at 60Hz.