beautypg.com

11 auxiliary parameters, 1 slip compensation (pr. 95 , pr. 96 , pr. 97 ) – MITSUBISHI ELECTRIC FR-S520E User Manual

Page 134

background image

124

Auxiliary parameters

2.11 Auxiliary parameters

2.11.1 Slip compensation (Pr. 95

, Pr. 96

, Pr. 97

)

*When this value is made smaller, response will be faster.

However, as load inertia is greater, a regenerative overvoltage (OVT) error is
more liable to occur.

The inverter output current may be used to assume motor slip to keep the motor
speed constant.

Parameter

Name

Factory

Setting

Setting Range

Remarks

95

Rated motor slip

- - -

0 to 50%, - - -

Setting is enabled
when Pr. 30 = "1"

96

Slip compensation time
constant

0.5s

0.01 to 10s

97

Constant-output region slip
compensation selection

- - -

0, - - -

Rated slip =

Synchronous speed at base frequency - rated speed

×100[%]

Synchronous speed at base frequency

Parameter

Setting

Function

95

0.01 to 50%

Used to set the rated motor slip.

0, - - -

Slip compensation is not made.

96

0.01 to 10s

Used to set the slip compensation response time. (*)

97

0

Slip compensation is not made in the constant output range
(frequency range above the frequency set in Pr. 3).

- - -

Slip compensation is made in the constant output range.

REMARKS

When making slip compensation at 60Hz, set the maximum frequency (Pr. 1) to slightly higher
than 60Hz.
In the factory setting status, it is clamped at 60Hz.

This manual is related to the following products: