Operation selection function parameters

(4) I/O signals

• Enter the set point across inverter terminals 2-5 or in Pr. 93 and enter the measured

value signal across inverter terminals 4-5.

• To exercise PID control, turn on the X14 signal. When this signal is off, PID control is

not exercised.

(5) Parameter setting

Signal

Terminal Used

Function

Description

Input

X14

Depending on

Pr. 60 to Pr. 63

PID control

selection

Turn on X14 to exercise PID control.

2

2

Set point input

Enter the set point for PID control.

4

4

Measured value

input

Enter the 4 to 20mADC measured value

signal from the detector.

Output

FUP

Depending on

Pr. 64, Pr. 65

Upper limit output

Output to indicate that the measured value

signal exceeded the upper limit value.

FDN

Lower limit output

Output to indicate that the measured value

signal exceeded the lower limit value.

RL

Forward (reverse)

rotation direction

output

"Hi" is output to indicate that the output

indication of the parameter unit is forward

rotation (FWD) or "Low" to indicate that it is

reverse rotation (REV) or stop (STOP).

Item

Entry

Description

Set point

Across

terminals 2-5

Set 0V as 0% and 5V as 100%.

When "0" is set in Pr. 73 (5V
selected for terminal 2).

Set 0V as 0% and 10V as 100%.

When "1" is set in Pr. 73 (10V
selected for terminal 2).

Pr. 93

Set the set point (%) in Pr. 93.

Measured

value

Across

terminals 4-5

4mA is equivalent to 0% and 20mA to 100%.

Parameter

Number

Name

Setting

Description

88

PID action

selection

20

For heating, pressure control, etc. PID reverse action

21

For cooling, etc.

PID forward action

89

PID

proportional

band

0.1 to 999%

If the proportional band is narrow (parameter setting is

small), the manipulated variable varies greatly with a slight

change of the measured value. Hence, as the proportional

band narrows, the response sensitivity (gain) improves but

the stability deteriorates, e.g. hunting occurs.

Gain K = 1/proportional band

- - -

No proportional control

90

PID integral

time

0.1 to 999s

Time required for the integral (I) action to provide the

same manipulated variable as that for the proportional

(P) action. As the integral time decreases, the set point

is reached earlier but hunting occurs more easily.

- - -

No integral control.