Troubleshooting

................ Check the Pr. 79 setting.

When the Pr. 79 "operation mode selection"
setting is "0", switching input power on places
the inverter in the external operation mode.

Press the

to switch to the PU operation

mode.
For other settings (1 to 8), the operation mode
is limited accordingly.
(For details of Pr. 79, refer to page 113.)

PU

EXT

2. Parameter setting

3.2.8 Operation mode is not changed properly

If the operation mode does not change correctly, check the following:

............ Check that the STF or STR signal is off.

When it is on, the operation mode cannot be
changed.

1. External input signal

3.2.9 Operation panel display is not operating

Make sure that terminals PC-SD are not shorted.

Make sure that the connector is fitted securely across terminals P-P1.

Check that the

(

) was pressed.

SET

WRITE

3.2.10 Parameter write cannot be performed

Make sure that operation is not being performed (signal STF or STR is not ON).

Make sure that you are not attempting to set the parameter outside the setting
range.

Make sure that you are not attempting to set the parameter in the external
operation mode.

Check Pr. 77 "parameter write disable selection".

3.2.11 Motor produces annoying sound

Check the Pr. 70 "Soft-PWM setting" and Pr. 72 "PWM frequency selection"
settings.
Make sure that the deceleration time is not too short.