Operation selection function parameters

2

F

UNCT

IO

NS

(6) Adjustment procedure

91

PID upper

limit

0 to 100%

Set the upper limit. If the feedback value exceeds the

setting, the FUP signal is output. (Measured value of

4mA is equivalent to 0% and 20mA to 100%.)

- - -

No function

92

PID lower

limit

0 to 100%

Set the lower limit. (If the measured value falls below

the setting, the FDN signal is output. In this case, the

measured value of 4mA is equivalent to 0% and 20mA

to 100%.)

- - -

No function

93

PID action

set point for

PU operation

0 to 100%

Valid only when Pr. 79 = "3" (n9 = 0 for computer link

operation) under the PU command in the PU operation

or PU/external combined mode. (When the computer

has the speed command source in the computer link

operation mode (NET))

For external operation, the voltage across 2-5 is the set

point.

(C3 value is equivalent to 0% and C4 value to 100%.)

94

PID

differential

time

0.01 to 10s

Time required for the differential (D) action to provide

the same measured value as that for the proportional

(P) action. As the differential time increases, greater

response is made to a deviation change.

- - -

No differential control.

Parameter

Number

Name

Setting

Description

Turn on X14 signal.

Parameter setting

Terminal setting

Run

Adjust the PID control parameters, Pr. 88 to Pr. 94.

Set the I/O terminals for PID control.
(Use Pr. 64 and Pr. 65 (output terminal function selection) to set the
FUP and FDN signals.)
(Use any of Pr. 60 to Pr. 63 (input terminal function selection) to set
the X14 signal.)