3 motor primary resistance (pr. 99 ), 12 maintenance parameters, 1 maintenance output function (h1, h2 ) – MITSUBISHI ELECTRIC FR-S520E User Manual
Page 136: Age 126), 1 maintenance output function (h1 , h2 )
![background image](/manuals/117960/136/background.png)
126
Maintenance parameters
2.11.3 Motor primary resistance (Pr. 99
)
2.12 Maintenance parameters
2.12.1 Maintenance output function (H1
, H2
)
The parameter numbers in parentheses are those for use with the parameter unit (FR-
PU04).
Generally this parameter need not be set. At the factory setting of "- - -", the
standard motor constant of the motor capacity set in Pr. 98 (including that of the
constant-torque motor) is used.
Parameter
Name
Factory
Setting
Setting
Range
Remarks
99
Motor primary
resistance
- - -
0 to 50
Ω,
- - -
Setting is enabled when Pr. 30 = "1"
♦Related parameters♦
• Applied motor setting
⇒
Pr. 71 "applied motor" (refer to page 73)
• Automatic torque boost selection
⇒
Pr. 98 "automatic torque boost selection" (refer to page 125)
The maintenance timer alarm signal (Y95) is output when the cumulative
energization time (H1 "maintenance timer") of the inverter reaches the time set
in H2 "maintenance alarm output set time". (Used to alert the operator of the
main circuit smoothing capacitor life expiration, for example.)
Parameter
Name
Factory
Setting
Setting
Range
Remarks
H1 (503)
Maintenance timer
0
0 to 999
Write disabled
Setting can be
made when Pr.
30 = "1"
H2 (504)
Maintenance alarm
output set time
36
(36000h)
0 to 999, - - -
- - -: Function as
36000h
Initial power-on
Maintenance timer
H1(Pr.503)
Y95 output/indication
OFF
ON
H2(Pr. 504)
999000h