beautypg.com

MITSUBISHI ELECTRIC FR-S520E User Manual

Page 117

background image

107

Operation selection function parameters

2

F

UNCT

IO

NS

2.10.2 PWM carrier frequency and long wiring mode (Pr. 70

, Pr. 72

)

• By parameter setting, you can set whether to exercise Soft-PWM control that

changes the motor tone or select with or without long wiring mode.

• Soft-PWM control is a control system that changes the motor noise from a metallic tone into an

unoffending complex tone.

• Surge voltage is suppressed regardless of wiring length in the long wiring mode. (When

operating the 400V motor with wiring length of 40m or longer, select the long wiring mode.)

Refer to

(page 73).

You can change the motor sound.

Parameter

Name

Factory

Setting

Setting

Range

Remarks

70

Soft-PWM setting

1

0, 1, 10, 11 Setting is enabled when

Pr. 30 = "1"

72

PWM frequency selection

1

0 to 15

Pr.70

Setting

Description

Soft-PWM

Long wiring mode

Remarks

0

Invalid

Invalid



1

Valid

(When Pr. 72 setting

= any of "0" to "5")

Invalid



10

Invalid

Valid

•When Pr. 72 "PWM frequency

selection" = 1 or more, the PWM
carrier frequency is constant at
1kHz. (When "0" is set, the PWM
carrier frequency is constant at
0.7kHz.)

11

Valid

Valid

CAUTION

1.The output voltage at the rated frequency drops by a maximum of 5V.
2.For the 400V class, use an insulation-enhanced motor.

Refer to page 24 for an inverter-driven 400V class motor.

Pr.72 Setting

Description

0 to 15

PWM carrier frequency can be changed.
The setting displayed is in [kHz].
Note that 0 indicates 0.7kHz and 15 indicates 14.5kHz.

REMARKS

•An increased PWM frequency will decrease the motor sound but increase noise and leakage

currents. Therefore, perform the reduction techniques. (Refer to page 18.)

•Metallic sound may be generated from the motor at sudden deceleration but it is not a fault.

This manual is related to the following products: