Main circuit terminals

(3) Selecting the rated sensitivity current for the earth leakage circuit

breaker

When using the earth leakage circuit breaker with the inverter circuit, select its rated
sensitivity current as follows, independently of the PWM carrier frequency:

Breaker for harmonic and surge
Rated sensitivity current:
I

∆n ≥ 10 × (lg1+Ign+lg2+lgm)

Standard breaker
Rated sensitivity current:
I

∆n ≥ 10 × {lg1+lgn+3 × (lg2+lgm)}

lg1, lg2 : Leakage currents of cable

path during commercial
power supply operation

lgn*

: Leakage current of noise

filter on inverter input side

lgm

: Leakage current of motor

during commercial power
supply operation

* Note the leakage current value of the

noise filter installed on the inverter
input side.

Breaker for harmonic and

surge

Standard breaker

Leakage current (Ig1) (mA)

20

×

5m

= 0.10

1000m

Leakage current (Ign) (mA)

0 (without noise filter)

Leakage current (Ig2) (mA)

20

×

70m

= 1.40

1000m

Motor leakage
current (Igm) (mA)

0.16

Total leakage current (mA)

1.66

4.78

Rated sensitivity current
(mA) (

Ig × 10)

30

100

Motor capacity (kW)

Example of leakage
current per 1km in cable
path during commercial
power supply operation
when the CV cable is
routed in metal conduit

Leakage current (mA)

Leakage current (mA)

Cable size (mm)

2

Leakage current
example of three-phase
induction motor
during commercial
power supply
operation

(200V 60Hz)

(200V 60Hz)

0

20

40

60

80

100

120

2 3.5 8 142238 80

5.5

3060100

150

1.5 3.7

2.2

7.5 1522

11

37

30

55

45

5.5

18.5

2.0

1.0
0.7
0.5
0.3

0.2

0.1

NV

Ig1

Ign

Ig2

Igm

2mm ×5m

2mm ×70m

IM

3
200V
1.5kW

Inver-
ter

Noise

filter

2

2