beautypg.com

MITSUBISHI ELECTRIC FR-S520E User Manual

Page 27

background image

17

Main circuit terminals

1

WI

RING

1.2.7

Regarding the installation of the power factor
improving reactor

When the inverter is installed near a large-capacity power transformer (500kVA or
more with the wiring length of 10m or less) or the power capacitor is to be switched, an
excessive peak current will flow in the power supply input circuit, damaging the
converter circuit. In such a case, always install the power factor improving reactor (FR-
BEL(-H) or FR-BAL(-H)).

REMARKS

* When connecting the FR-BEL(-H), remove the jumper across terminals P-P1.

The wiring length between the FR-BEL(-H) and the inverter should be 5m maximum and as
short as possible.
Use the cables which are equal in size to those of the main circuit. (Refer to page 8)

NFB

Inverter

FR-BAL(-H)

Power
supply

R

S

T

Z

Y

X

U

V

W

P1

FR-BEL(-H)(*)

P

R

S
T

0

10

Wiring length (m)

500

1500

1000

P

o

w

e

r s

u

pp

ly

e

qui

p

m

en

t

cap

a

ci

ty

(kV

A

)

Power factor
improving reactor
installation range

This manual is related to the following products: