beautypg.com

MITSUBISHI ELECTRIC FR-S520E User Manual

Page 48

background image

38

How to use the input signals (assigned terminals
RL, RM, RH, STR)

1.5.4

Start self-holding selection (STOP signal):

Pr. 60 to Pr. 63

setting

"5"

1.5.5

Output shut-off (MRS signal):

Pr. 60 to Pr. 63 setting

"6"

Short the output stop terminal MRS-SD during inverter output to cause the inverter to
immediately stop the output. Open terminals MRS-SD to resume operation in about
10ms. Terminal MRS may be used as described below:

This connection example is used when you want
to self-hold the start signal (forward rotation,
reverse rotation).
* Connected to the STOP signal to avoid

forward or reverse rotation if forward or
reverse rotation and stop are turned on
simultaneously.

(1) To stop the motor by

mechanical brake (e.g.
electromagnetic brake)

Terminals MRS-SD must be
shorted when the mechanical
brake is operated and be opened
before motor restart.

(2) To provide interlock to

disable operation by the
inverter

After MRS-SD have been shorted,
the inverter cannot be operated if
the start signal is given to the
inverter.

(3) To coast the motor to stop

The motor is decelerated according to the preset deceleration time and is stopped
by operating the DC injection brake at 3Hz or less. By using terminal MRS, the
motor is coasted to a stop.

STF

STR

Stop

Forward

rotation
Reverse

rotation

(Wiring example for sink logic)

STOP

*

SD

Out

put

f

re

q

u

enc

y

Motor coasted
to stop

0.5Hz

Across
STF-
(STR)

ON

ON

Pr. 13

"starting
frequency"

Across
MRS -SD

SD

This manual is related to the following products: