MITSUBISHI ELECTRIC FR-S520E User Manual
Page 54
44
Connection to the Stand-Alone Option
1.6.3
Connection of the high power factor converter (FR-HC)
When connecting the high power factor converter (FR-HC) to suppress power supply
harmonics, perform wiring securely as shown below. Incorrect connection will damage
the high power factor converter and inverter.
CAUTION
1. Use sink logic (factory setting) when the FR-HC is connected. The FR-HC
cannot be connected when source logic is selected.
2. The power input terminals R, S, T must be open. Incorrect connection will
damage the inverter. Opposite polarity of terminals N, P will damage the
inverter.
3. The voltage phases of terminals R, S, T and terminals R4, S4, T4 must be
matched before connection.
4. Use Pr. 60 to Pr. 63 (input terminal function selection) to assign the terminals
used for the RES and MRS signals.
5. Do not insert NFB between terminals P-N (P - P, N - N)
6. The N terminal is not provided for the FR-S520E-0.1K to 0.75K.
From FR-HCL02
Power
supply
NFB
R
S
T
R4
S4
T4
N
P
Y1 or Y2
RDY
RSO
SE
High power factor converter (FR-HC)
Inverter
MRS (Caution 4)
RES (Caution 4)
SD
External box
FR-HCL01
R4
S4
T4
R3
S3
T3
R2
S2
T2
R
S
T
MC2
MC1
MC1 MC2
(Caution 2)
(Caution 1)
(Caution 2)
(Caution 5)
(Caution 2)
T
S
R
P
N (Caution 6)