beautypg.com

2 connection of the brake unit (bu type) – MITSUBISHI ELECTRIC FR-S520E User Manual

Page 53

background image

43

Connection to the Stand-Alone Option

1

WI

RING

1.6.2

Connection of the brake unit (BU type)

Connect the BU type brake unit correctly as shown below. Incorrect connection will
damage the inverter. Remove jumpers across terminals HB-PC and TB-HC and
connect a jumper across terminals PC-TB of the brake unit.

CAUTION

1. The wiring distance between the inverter, brake unit and discharge resistor

should be within 2m. If twisted wires are used, the distance should be within
5m.

2. If the transistors in the brake unit should become faulty, the resistor can be

unusually hot, causing a fire. Therefore, install a magnetic contactor on the
inverter's power supply side to shut off a current in case of fault.

3. The N terminal is not provided for the FR-S520E-0.1K to 0.75K.
4. When the power supply is 400V class, install a step-down transformer.

Motor

Inverter

BU(-H) type brake unit

T(Caution 4)

MC

U

V

W

HC

HB

HA

TB

P

OCR

PR

NFB

PC

ON

OFF

MC

OCR

N

MC

Remove
jumpers.

IM

Discharge resistor

Connect a
jumper.

Power
supply

(Caution 3)

R/L1

S/L2

T/L3

N/-

P/+

This manual is related to the following products: