115

Operation selection function parameters

2

F

UNCT

IO

NS

(1) PU operation interlock

PU operation interlock forces the operation mode to be changed to the external
operation mode when the MRS signal switches off. This function prevents the
inverter from being inoperative by the external command if the mode is
accidentally left unswitched from the PU operation mode.

1) Preparation
•Set "7" (PU operation interlock) in Pr. 79.

•Set the terminal used for MRS signal input with any of Pr. 60 to Pr. 63 (input terminal

function selection).
Refer to page 102 for Pr. 60 to Pr. 63 (input terminal function selection).

2) Function

CAUTION

When terminal assignment is changed using Pr. 60 to Pr. 63, the other
functions may be affected.
Check the functions of the corresponding terminals before making settings.

MRS Signal

Function/Operation

ON

Output stopped during external operation.
Operation mode can be switched to PU operation mode.
Parameter values can be rewritten in PU operation mode.
PU operation allowed.

OFF

Forcibly switched to external operation mode.
External operation allowed.
Switching to PU operation mode inhibited.

Operating Condition

MRS

Signal

Operation

Mode

(*2)

Operating Status

Parameter

Write

Switching to

PU Operation

Mode

Operation

mode

Status

PU

During

stop

ON

→ OFF

(*1)

PU

External

During stop

Allowed

disallowed

Disallowed

During

operation

ON

→ OFF

(*1)

If external
operation
frequency setting
and start signal are
entered, operation
is performed in that
status.

Allowed

disallowed

Disallowed

External

During

stop

OFF

→ ON

External

During stop

Disallowed

disallowed

Allowed

ON

→ OFF

Disallowed

disallowed

Disallowed

During

operation

OFF

→ ON

During operation

output stop

Disallowed

disallowed

Disallowed

ON

→ OFF

Output stop

operation

Disallowed

disallowed

Disallowed