138

Communication parameters

To make communication between the personal computer and inverter, initialization of
the communication specifications must be made to the inverter. If initial setting is not
made or there is a setting fault, data transfer cannot be made.
*

After making the initial setting of the parameters, always reset the inverter. After you

have changed the communication-related parameters, communication cannot be
made until the inverter is reset.

Parameter

Description

Setting

Description

n1

Communication

station number

0 to 31

Station number specified for communication from
the RS-485 connector.
Set the inverter station numbers when two or more
inverters are connected to one personal computer.

n2

Communication

speed

48

4800bps

96

9600bps

192

19200bps

n3

Stop bit length/

data length

8 bits

0

Stop bit length 1 bit

1

Stop bit length 2 bits

7 bits

10 Stop bit length 1 bit

11 Stop bit length 2 bits

n4

Parity check

presence/

absence

0

Absent

1

Odd parity present

2

Even parity present

n5

Number of

communication

retries

0 to 10

Set the permissible number of retries at occurrence
of a data receive error.
If the number of consecutive errors exceeds the
permissible value, the inverter will come to an alarm
stop (OPT).

---

(65535)

If a communication error occurs, the inverter will not
come to an alarm stop. At this time, the inverter can
be coasted to a stop by MRS or RES input.
During a communication error (H0 to H5), the minor
fault signal (LF) is switched on. Allocate the used
terminal with any of Pr. 64, Pr. 65 (output terminal
function selection).

n6

Communication

check time

interval

0

No communication

0.1 to 999

Set the communication check time [s] interval.
If a no-communication state persists for longer than
the permissible time, the inverter will come to an
alarm stop (OPT).

---

Communication check suspension.

n7

Waiting time

setting

0 to 150

Set the waiting time between data transmission to
the inverter and response.

---

Set with communication data.

n11

CR/LF selection

0

Without CR/LF

1

With CR, without LF

2

With CR/LF