7 program table mode (mode 0), 1 program table mode setting, 2 program operation inputs setting – Yaskawa Sigma II Indexer User Manual
Page 102

Sigma II Indexer User’s Manual
Program Table Mode (Mode 0)
5-47
5.7
Program Table Mode (Mode 0)
5.7.1 Program Table Mode Setting
Set the /MODE 0/1 input signal to Mode 0 for Program Table Mode. The following parame-
ter is used to define the /MODE 0/1 input signal.
5.7.2 Program Operation Inputs Setting
The following parameters are used to define the inputs used in the program table operation.
Table 5.4:
Parameter
Signal
Pin No.
Setting
Default
Pn803
/Mode 0/1
CN4-3
0 = Input signal Closed = Mode 0
1 = Input signal Open = Mode 0
2 = Always Mode 0
3 = Always Mode 1
0
Table 5.5:
Parameter
Signal
Pin No.
Setting
Default
Pn804
/START – STOP
CN4-5
0 = Input Signal Closed = Motor Start, Program Start
1 = Input Signal Open = Motor Stop, Program Stop
2 or 3 = No Program Start
0
Pn805
/PGMRES
CN4-7
0 = Input Signal Open
o
Closed = Program Reset
1 = Input Signal Closed
o
Open = Program Reset
2 or 3 = No Program Reset
0
Pn806
/SEL0
CN4-9
0 = Input signal Closed = Program Select
1= Input Signal Open = Program Select
2 = Always Program Select
3 = No Program Select
0
Pn807
/SEL1
CN4-11
Pn808
/SEL2
CN4-13
Pn809
/SEL3
CN4-15
Pn80A
/SEL4
CN4-17
Pn833
/SEL5
CN1-41
Pn834
/SEL6
CN1-45