beautypg.com

SMA SC 500CP XT User Manual

Page 97

background image

10.3.3.6 Reactive Power Setpoint via Standard Signal: VArCnstNomAnIn Mode

The reactive power setpoint is set at the input terminals for the setpoints via an analog signal. This is usually
implemented by a ripple control signal. The analog value is converted into a reactive power setpoint. The electrical
current strength of the connected signal determines the setpoint. The analog measured values must be between
4 mA and 19 mA. If the analog signal is less than 2 mA, an error message will be displayed in the instantaneous value
Q‑VArModFailStt.

Signal

Power limit

Description

< 2 mA

Last valid mean value or 0 kVAr after
restart

Signal is in the invalid range.

2 mA to 4 mA

Qmax / underexcited

The maximum amount of negatively excited reactive
power is fed in.

4 mA

Qmax / underexcited

Start point of the characteristic curve

The maximum amount of negatively excited reactive
power is fed in.

11.5 mA

0 kVAr

Zero-crossing of the characteristic curve

No reactive power is fed in.

> 19 mA

Qmax / overexcited

End point of the characteristic curve

The maximum amount of positively excited reactive
power is fed in.

The analog value is converted to a setpoint for power limitation. Here, the parameter Qmax forms the end point of the
linear characteristic curve.

Figure 23: Limitation of the reactive power to the parameter Qmax

10.3.3.7 Reactive Power Setpoint via Displacement Power Factor cos φ: PFCnst Mode

The reactive power setpoint is set via the parameters PF‑PF and PF‑PFExt. The parameter PF‑PF indicates the
displacement power factor cos φ and the parameter PF‑PFExt indicates the degree of overexcitation or
underexcitation.

10 Function Description

SMA Solar Technology AG

User Manual

97

SCCPXT-BA-E4-en-54