7.5.5

Error Numbers 6xx to 9xx - Disturbance on the Inverter

Error no. Explanation

Inverter behavior

Corrective measures

S1

S2

R

6002

Calibration data cannot be
loaded.

Q

Q

• Contact SMA Service Line.

6113

Data block cannot be loaded from
EEPROM or channel list has
changed (e.g. after firmware up-
date)

W

W

• Contact SMA Service Line.

6115

Setting of hardware thresholds on
D/A converters is not possible.

5 min

5 min

x

• Contact SMA Service Line.

6116

Real-time clock has not initialized.

W

W

• Contact SMA Service Line.

6117

Device address not recognized.

5 min

5 min

x

• Contact SMA Service Line.

6119

Data structure for communication
between operation control unit
and digital signal processor is in-
valid.

5 min

5 min

x

• Contact SMA Service Line.

6120

Watchdog tripping error

30 s

W

• Contact SMA Service Line.

6121

No response from watchdog

30 s

W

• Contact SMA Service Line.

6122

Ten internal monitoring errors have
occurred in succession.

W

5 min

• Contact SMA Service Line.

6128

General error

5 min

5 min

x

• Contact SMA Service Line.

6404

Overcurrent at line conductor L1,
L2 or L3

C

Q

x

• Contact SMA Service Line.

6405

Overvoltage in the DC link of the
inverter bridge

30 s

5 min

• Contact SMA Service Line.

6410

24 V supply voltage is invalid.

5 min

5 min

x

• Contact SMA Service Line.

6417

15 V supply voltage is invalid.

5 min

5 min

x

• Contact SMA Service Line.

6418

Overtemperature of the inverter
bridge

5 min

15
min

• Contact SMA Service Line.

6422

Inverter bridge in undefined state

30 s

5 min

• Contact SMA Service Line.

6423

Overtemperature in the switch
cabinet

5 min

30
min

• Contact SMA Service Line.

6425

Synchronization error with utility
grid

30 s

5 min

x

• Contact SMA Service Line.

6427

Sensor error of DC voltage mea-
surement

30 s

C

• Contact SMA Service Line.

6440

The MV transformer is no longer
hermetically sealed.

30 s

5 min

• Check the MV transformer.