The input currents are monitored by the current transformers installed on the DC rails. The current transformers measure
the input currents and forward the measured values via I/O interface to the communication unit. The communication
unit continually calculates the mean values of the input currents and compares the current measured values with the
mean values. If an input current falls below the mean value by a user-defined tolerance, the communication unit issues
a message. For correct analysis of the input currents, the following must be set:
• Maximum input current for each input
• Tolerance in percent by which the input current may deviate from the mean value
When a deviation occurs, the error message is displayed in the event report, if the error analysis is activated. It can
also be sent to Sunny Portal or, depending on the settings, it can be forwarded by e-mail.
10 Function Description
SMA Solar Technology AG
User Manual
SCCPXT-BA-E4-en-54
116
- SC 630CP XT SC 720CP XT SC 760CP XT SC 800CP XT SC 850CP XT SC 900CP XT SC 500CP XT Maintenance Manual SC 630CP XT Maintenance Manual SC 720CP XT Maintenance Manual SC 760CP XT Maintenance Manual SC 800CP XT Maintenance Manual SC 850CP XT Maintenance Manual SC 900CP XT Maintenance Manual SC 1000CP XT SC 1000CP XT Maintenance Manual