2 checking the heating elements and hygrostat, Checking the heating elements and hygrostat – SMA SC 500CP XT User Manual
Page 34
Procedure:
1. Switch the inverter to Stop.
2. Connect the supply voltage (see Section 5.3.1, page 53).
☑ The fans start to run for a few moments.
✖ The fans do not start up?
• Contact SMA Service Line.
4.5.2
Checking the Heating Elements and Hygrostat
Figure 11: Position of the heating element and the hygrostat
Position
Designation
A
Hygrostat
B
Heating element
Danger to life due to electric shock or electric arc if live components are touched
• Switch off the inverter and wait at least 15 minutes before opening it to allow the capacitors to discharge
completely.
• Disconnect the inverter (see Section 5, page 51).
Risk of burns due to hot components
Some components of the product can get very hot during operation. Touching these components can cause burns.
• Observe the warnings on all components.
• During operation, do not touch any components marked with such warnings.
• Wear suitable personal protective equipment for all work on the product.
4 Commissioning
SMA Solar Technology AG
User Manual
SCCPXT-BA-E4-en-54
34
- SC 630CP XT SC 720CP XT SC 760CP XT SC 800CP XT SC 850CP XT SC 900CP XT SC 500CP XT Maintenance Manual SC 630CP XT Maintenance Manual SC 720CP XT Maintenance Manual SC 760CP XT Maintenance Manual SC 800CP XT Maintenance Manual SC 850CP XT Maintenance Manual SC 900CP XT Maintenance Manual SC 1000CP XT SC 1000CP XT Maintenance Manual