beautypg.com

SMA SC 500CP XT User Manual

Page 124

background image

Name

Description

Value/range

Explanation

Default
value

P-W

Active power limit in kW

The active power cannot
exceed Pmax.

0 kW to 1,000 kW

Sunny Central 500CP XT

550 kW

0 kW to 1,000 kW

Sunny Central 630CP XT

700 kW

0 kW to 1,000 kW

Sunny Central 720CP XT

792 kW

0 kW to 1,000 kW

Sunny Central 760CP XT

836 kW

0 kW to 1,000 kW

Sunny Central 800CP XT

880 kW

0 kW to 1,000 kW

Sunny Central 850CP XT

935 kW

0 kW to 1,000 kW

Sunny Central 900CP XT

990 kW

P-WNom

Limitation of active
power in %

0 % … 100 %

100 %

WCtlHzMod
**

Activation of frequency-
dependent active power
limitation

Off

Deactivated

Country-
specific

CurveHys

Procedure with hysteresis

Curve

Procedure without hysteresis

P-HzStr**

Starting point of fre-
quency control

Country-specific

Country-
specific

P-HzStop**

End point of frequency
control

Country-specific

Country-
specific

P-HzStopMin
**

Minimum frequency at
end point of frequency
control

Country-specific

Country-
specific

P-WGra**

Gradient of active power
limitation in case of ac-
tive power limitation de-
pendent on the fre-
quency

1%/Hz to 100%/Hz

40%/Hz

Qlimit*

Reactive power of device 0 kVAr to 245 kVAr

Sunny Central 500CP XT

245 kVAr

0 kVAr to 310 kVAr

Sunny Central 630CP XT

310 kVAr

0 kVAr to 346 kVAr

Sunny Central 720CP XT

346 kVAr

0 kVAr to 365 kVAr

Sunny Central 760CP XT

365 kVAr

0 kVAr to 385 kVAr

Sunny Central 800CP XT

385 kVAr

0 kVAr to 409 kVAr

Sunny Central 850CP XT

409 kVAr

0 kVAr to 433 kVAr

Sunny Central 900CP XT

433 kVAr

11 Operating Data and Parameters

SMA Solar Technology AG

User Manual

SCCPXT-BA-E4-en-54

124