SMA SC 500CP XT User Manual
Page 124
Name
Description
Value/range
Explanation
Default
value
P-W
Active power limit in kW
The active power cannot
exceed Pmax.
0 kW to 1,000 kW
Sunny Central 500CP XT
550 kW
0 kW to 1,000 kW
Sunny Central 630CP XT
700 kW
0 kW to 1,000 kW
Sunny Central 720CP XT
792 kW
0 kW to 1,000 kW
Sunny Central 760CP XT
836 kW
0 kW to 1,000 kW
Sunny Central 800CP XT
880 kW
0 kW to 1,000 kW
Sunny Central 850CP XT
935 kW
0 kW to 1,000 kW
Sunny Central 900CP XT
990 kW
P-WNom
Limitation of active
power in %
0 % … 100 %
‒
100 %
WCtlHzMod
**
Activation of frequency-
dependent active power
limitation
Off
Deactivated
Country-
specific
CurveHys
Procedure with hysteresis
Curve
Procedure without hysteresis
P-HzStr**
Starting point of fre-
quency control
Country-specific
‒
Country-
specific
P-HzStop**
End point of frequency
control
Country-specific
‒
Country-
specific
P-HzStopMin
**
Minimum frequency at
end point of frequency
control
Country-specific
‒
Country-
specific
P-WGra**
Gradient of active power
limitation in case of ac-
tive power limitation de-
pendent on the fre-
quency
1%/Hz to 100%/Hz
‒
40%/Hz
Qlimit*
Reactive power of device 0 kVAr to 245 kVAr
Sunny Central 500CP XT
245 kVAr
0 kVAr to 310 kVAr
Sunny Central 630CP XT
310 kVAr
0 kVAr to 346 kVAr
Sunny Central 720CP XT
346 kVAr
0 kVAr to 365 kVAr
Sunny Central 760CP XT
365 kVAr
0 kVAr to 385 kVAr
Sunny Central 800CP XT
385 kVAr
0 kVAr to 409 kVAr
Sunny Central 850CP XT
409 kVAr
0 kVAr to 433 kVAr
Sunny Central 900CP XT
433 kVAr
11 Operating Data and Parameters
SMA Solar Technology AG
User Manual
SCCPXT-BA-E4-en-54
124
- SC 630CP XT SC 720CP XT SC 760CP XT SC 800CP XT SC 850CP XT SC 900CP XT SC 500CP XT Maintenance Manual SC 630CP XT Maintenance Manual SC 720CP XT Maintenance Manual SC 760CP XT Maintenance Manual SC 800CP XT Maintenance Manual SC 850CP XT Maintenance Manual SC 900CP XT Maintenance Manual SC 1000CP XT SC 1000CP XT Maintenance Manual