4.3.3

Checking the High-Current Contacts Made at the Installation Site

Test point

Tasks

Cables

Ensure that the cable type and cross-section, the number of cables and the labeling comply
with the specifications in the schematic diagram.

High-current contact

Check whether the high-current contacts established at the installation site are tightened to
the correct torque. If the torque is not correct, release and clean the high-current contact and
tighten with the required torque.

Terminal lugs

Ensure that the terminal lugs are crimped edge to edge.

Cable support rails

Ensure that the cables are adequately attached to the cable support rails.

4.3.4

Checking the High-Current Contacts Made at the Factory

High-current contacts made at the factory

High-current contacts made at the factory are marked off. Providing that the marking is not damaged and runs
across the bolted connection as shown in the figure, this means that the torque complies with the specifications.

Procedure:

• Check whether the high-current contacts made at the factory

are correctly marked off.

If a high-current contact is not correctly marked off, release the high-current contact, tighten with the required
torque and mark off again.

4.3.5

Checking the Settings of the Switching Units

Test Point

Tasks

AC circuit breaker

Ensure that the settings comply with the specifications in the schematic diagram.

GFDI

Hygrostat