7.3

Reading Off Disturbance Messages

7.3.1

Reading Off Error Messages via Touch Display

If an error occurs, a warning symbol is shown on the touch display.

Procedure:

• Select the warning symbol.

☑ The touch display lists the error number, waiting time, error message and the necessary corrective measure to

eliminate the disturbance.

7.3.2

Reading Off Disturbance Messages via the User Interface

1. Log into the user interface (see Section 9.4.1, page 81).

2. To display the error number, select the instantaneous value ErrNo in the instantaneous value view.

3. To display the delay time, select the instantaneous value TmsRmg in the instantaneous value view.

4. To display the error message, select the instantaneous value Msg in the instantaneous value view.

5. To display the corrective measure, select the instantaneous value Dsc in the instantaneous value view.

7.3.3

Displaying the Event Report

7.3.3.1

Enabling Automatic Read-Out of Events

1. Log into the user interface (see Section 9.4.1, page 81).

2. Select Sunny Central > Recording.

3. In the field Collect automatically fault logs, select yes.

4. Select the button [Save].

7.3.3.2

Displaying and Downloading the Event Report

The event report keeps a log of various events, e.g. errors and warnings. All events can be downloaded in a CSV file.
Upon delivery, the automatic transfer of the events is deactivated.

Procedure:

1. Log into the user interface (see Section 9.4.1, page 81).

2. In order to have the event report of the inverter displayed manually, proceed as follows:

• Select Sunny Central > Recording.

• In the field Manually requesting fault memory, select [Request].

• In the field Manually requesting event memory, select [Request].

3. Select Sunny Central > Events.

4. To download the events as CSV file, carry out the following steps:

• Select the button [Download].

• Choose the save location.

• Select the button [Save].