4 insulation monitoring – SMA SC 500CP XT User Manual
Page 138
Name
Description
Value/range
Explanation
Default
value
TrfVolExlLo*
Line-to-line voltage on un-
dervoltage side of exter-
nal transformer
1 V to 500 V
Sunny Central 500CP XT
270 V
Sunny Central 630CP XT
315 V
Sunny Central 720CP XT
324 V
Sunny Central 760CP XT
342 V
Sunny Central 800CP XT
360 V
Sunny Central 850CP XT
386 V
Sunny Central 900CP XT
405 V
* To change this parameter, you must enter the installer password.
** To view or change this parameter, you must enter the installer password.
11.2.1.4 Insulation monitoring
Name
Description
Value/range
Explanation
Default
value
IsoErrIgn*
Ignore insulation error
Off
Deactivated
Off
On
Activated
Run
Error is only ignored when the in-
verter is in feed-in operation.
RemMntSvc
PV array grounding is
deactivated.
Off
Deactivated
Off
On
Activated
RisoCtlWarn
Warning threshold for
the insulation monitoring
device iso-PV1685
0 kΩ to 500 kΩ
‒
45 kΩ
PvVtgRisoStart
Start voltage of insulation
measurement
0 V to 1,200 V
Sunny Central 500CP XT
500 V
Sunny Central 630CP XT
610 V
Sunny Central 720CP XT
675 V
Sunny Central 760CP XT
715 V
Sunny Central 800CP XT
760 V
Sunny Central 850CP XT
760 V
Sunny Central 900CP XT
770 V
PvVtgRisoDif
Differential voltage to
PvVtgStrLevMin for
switching from insulation
measurement to feed-in
operation
−250 V to +250 V
‒
0 V
11 Operating Data and Parameters
SMA Solar Technology AG
User Manual
SCCPXT-BA-E4-en-54
138
- SC 630CP XT SC 720CP XT SC 760CP XT SC 800CP XT SC 850CP XT SC 900CP XT SC 500CP XT Maintenance Manual SC 630CP XT Maintenance Manual SC 720CP XT Maintenance Manual SC 760CP XT Maintenance Manual SC 800CP XT Maintenance Manual SC 850CP XT Maintenance Manual SC 900CP XT Maintenance Manual SC 1000CP XT SC 1000CP XT Maintenance Manual