4 insulation monitoring – SMA SC 500CP XT User Manual

Page 138

background image

Name

Description

Value/range

Explanation

Default
value

TrfVolExlLo*

Line-to-line voltage on un-
dervoltage side of exter-
nal transformer

1 V to 500 V

Sunny Central 500CP XT

270 V

Sunny Central 630CP XT

315 V

Sunny Central 720CP XT

324 V

Sunny Central 760CP XT

342 V

Sunny Central 800CP XT

360 V

Sunny Central 850CP XT

386 V

Sunny Central 900CP XT

405 V

* To change this parameter, you must enter the installer password.

** To view or change this parameter, you must enter the installer password.

11.2.1.4 Insulation monitoring

Name

Description

Value/range

Explanation

Default
value

IsoErrIgn*

Ignore insulation error

Off

Deactivated

Off

On

Activated

Run

Error is only ignored when the in-
verter is in feed-in operation.

RemMntSvc

PV array grounding is
deactivated.

Off

Deactivated

Off

On

Activated

RisoCtlWarn

Warning threshold for
the insulation monitoring
device iso-PV1685

0 kΩ to 500 kΩ

45 kΩ

PvVtgRisoStart

Start voltage of insulation
measurement

0 V to 1,200 V

Sunny Central 500CP XT

500 V

Sunny Central 630CP XT

610 V

Sunny Central 720CP XT

675 V

Sunny Central 760CP XT

715 V

Sunny Central 800CP XT

760 V

Sunny Central 850CP XT

760 V

Sunny Central 900CP XT

770 V

PvVtgRisoDif

Differential voltage to
PvVtgStrLevMin for
switching from insulation
measurement to feed-in
operation

−250 V to +250 V

0 V

11 Operating Data and Parameters

SMA Solar Technology AG

User Manual

SCCPXT-BA-E4-en-54