10.3.5 Behavior in the Absence of Active and Reactive Power Setpoints
In the event of failure of setpoints for active and reactive power control, the inverter is capable of bridging the gap in
two ways:
• Use of last default values received:
As long as the inverter does not receive any updated default values, it will use the last value received (when
setpoint takes place via communication) and the last valid mean value (when using analog setpoints).
• Use of substitute values:
As long as the inverter does not receive any updated default values, it will utilize the specified substitute values for
active power limitation, reactive power setpoint and displacement power factor. In this case, different substitute
values can be configured for feed-in operation and grid monitoring.
The parameter PwrMonErrMod is used to configure whether the last default values (LastVal) or the configured
substitute values (SubVal) are to be used. This setting will be valid for both active and reactive power setpoints. The
substitute values are used when the time since receiving the last valid signal for default values as defined in the
parameter PwrMonErrTm has elapsed.
Setting
Description
LastVal
If specified via communication: utilization of the last value received
In case of analog setpoints: utilization of the last valid mean value
SubVal
Use of configured substitute values
The use of the substitute values is recommended when setpoints are effected via analog sig-
nals.
• P-WSubValRun: substitute value for active power limitation in feed-in operation
• P-WSubVal: substitute value for active power limitation outside of feed-in operation
• Q-VArSubValRun: substitute value for the reactive power setpoint in feed-in operation
• PF-PFSubValRun: substitute value for the displacement power factor in feed-in
operation
• PF-PFExtSubValR: substitute value for the excitation of the displacement power factor
in feed-in operation
• Q-VArSubVal: substitute value for the reactive power setpoint outside of feed-in
operation
• PF-PFSubVal: substitute value for the displacement power factor outside of feed-in
operation
• PF-PFExtSubVal: substitute value for the excitation of the displacement power factor
outside of feed-in operation
10.4
Structure of the Communication Network
In order to connect the inverter to a computer via the service interface or via the Internet, the communication unit must
be integrated in a system network. To enable several inverters to be operated in the same network, the communication
unit of each inverter must be assigned a unique network address.
10 Function Description
SMA Solar Technology AG
User Manual
SCCPXT-BA-E4-en-54
110
- SC 630CP XT SC 720CP XT SC 760CP XT SC 800CP XT SC 850CP XT SC 900CP XT SC 500CP XT Maintenance Manual SC 630CP XT Maintenance Manual SC 720CP XT Maintenance Manual SC 760CP XT Maintenance Manual SC 800CP XT Maintenance Manual SC 850CP XT Maintenance Manual SC 900CP XT Maintenance Manual SC 1000CP XT SC 1000CP XT Maintenance Manual