Error no. Explanation

Inverter behavior

Corrective measures

S1

S2

R

3501

The insulation monitoring device
has measured a too low ground-
ing resistance.

C

C

• Check the PV array for ground faults.

3502

The GFDI has tripped.

C

C

• Check the PV array for ground faults.

3504

The insulation monitoring device
has detected an insulation error.

If the parameter IsoErrIgn is set to
On, this error is ignored.

W

W

• Check the PV array for ground faults.

3507

A ground fault has occurred on
the ungrounded terminal of the PV
array.

Q

Q

• Check the PV array for ground faults.

3510

The inverter has detected an insu-
lation error on the inverter bridge.

Q

Q

• Check the PV array for ground faults.

3511

The inverter has detected an insu-
lation error.

W

W

• Check the PV array for ground faults.

3512

The Remote GFDI has detected a
permanent ground fault.

Q

Q

• Check the PV array for ground faults.

3515

A ground fault detected by
Soft Grounding has been ignored.

W

W

• Check the PV array for ground faults.

3517

Insulation measuring is being per-
formed.

W

W

3601

Leakage current to ground has oc-
curred in the PV array or the
threshold defined in parameter
RisoCtlWarn has been reached.

W

W

• Check the grounding and equipotential

bonding.

• Check the module wiring and system

design.

• Check the parameter RisoCtlWarn.

3803

The PV array current is too high.

1 min

D

• Check the DC input current.

• Check the module wiring and system

design.

4003

Reverse currents detected in the PV
array or DC connection polarity
reversed.

30 s

Q

• Check the PV modules for short circuits.

• Check the module wiring and system

design.

• Check the DC terminals for correct

polarity.

• Check the functionality of the entire

string.