Name

Description

Value/range

Explanation

Default
value

Q-VArSubVal

Substitute value for reac-
tive power setpoint out-
side of normal feed-in
operation during commu-
nication disturbance

−245 kVAr to
+245 kVAr

Sunny Central 500CP XT

0 kVAr

−310 kVAr to
+310 kVAr

Sunny Central 630CP XT

−346 kVAr to
+346 kVAr

Sunny Central 720CP XT

−365 kVAr to
+365 kVAr

Sunny Central 760CP XT

−385 kVAr to
+385 kVAr

Sunny Central 800CP XT

−409 kVAr to
+409 kVAr

Sunny Central 850CP XT

−433 kVAr to
+433 kVAr

Sunny Central 900CP XT

PF-PFSubVal

Substitute value for cos φ
outside of normal feed-in
operation during commu-
nication disturbance

The lower limit is defined
by the parameter PFAb-
sMin
.

0.5 … 1

1

PF-PFExtSubVal Substitute value for exci-

tation type during com-
munication disturbance

OvExt

Overexcited

OvExt

UnExt

Underexcited

Q-
VArSubValRun

Substitute value for reac-
tive power setpoint in
normal feed-in operation
during communication
disturbance

−245 kVAr to
+245 kVAr

Sunny Central 500CP XT

0 kVAr

−310 kVAr to
+310 kVAr

Sunny Central 630CP XT

−346 kVAr to
+346 kVAr

Sunny Central 720CP XT

−365 kVAr to
+365 kVAr

Sunny Central 760CP XT

−385 kVAr to
+385 kVAr

Sunny Central 800CP XT

−409 kVAr to
+409 kVAr

Sunny Central 850CP XT

−433 kVAr to
+433 kVAr

Sunny Central 900CP XT