Name
Description
Value/range
Explanation
Default
value
Q-VArSubVal
Substitute value for reac-
tive power setpoint out-
side of normal feed-in
operation during commu-
nication disturbance
−245 kVAr to
+245 kVAr
Sunny Central 500CP XT
0 kVAr
−310 kVAr to
+310 kVAr
Sunny Central 630CP XT
−346 kVAr to
+346 kVAr
Sunny Central 720CP XT
−365 kVAr to
+365 kVAr
Sunny Central 760CP XT
−385 kVAr to
+385 kVAr
Sunny Central 800CP XT
−409 kVAr to
+409 kVAr
Sunny Central 850CP XT
−433 kVAr to
+433 kVAr
Sunny Central 900CP XT
PF-PFSubVal
Substitute value for cos φ
outside of normal feed-in
operation during commu-
nication disturbance
The lower limit is defined
by the parameter PFAb-
sMin.
0.5 … 1
‒
1
PF-PFExtSubVal Substitute value for exci-
tation type during com-
munication disturbance
OvExt
Overexcited
OvExt
UnExt
Underexcited
Q-
VArSubValRun
Substitute value for reac-
tive power setpoint in
normal feed-in operation
during communication
disturbance
−245 kVAr to
+245 kVAr
Sunny Central 500CP XT
0 kVAr
−310 kVAr to
+310 kVAr
Sunny Central 630CP XT
−346 kVAr to
+346 kVAr
Sunny Central 720CP XT
−365 kVAr to
+365 kVAr
Sunny Central 760CP XT
−385 kVAr to
+385 kVAr
Sunny Central 800CP XT
−409 kVAr to
+409 kVAr
Sunny Central 850CP XT
−433 kVAr to
+433 kVAr
Sunny Central 900CP XT
11 Operating Data and Parameters
SMA Solar Technology AG
User Manual
SCCPXT-BA-E4-en-54
132
- SC 630CP XT SC 720CP XT SC 760CP XT SC 800CP XT SC 850CP XT SC 900CP XT SC 500CP XT Maintenance Manual SC 630CP XT Maintenance Manual SC 720CP XT Maintenance Manual SC 760CP XT Maintenance Manual SC 800CP XT Maintenance Manual SC 850CP XT Maintenance Manual SC 900CP XT Maintenance Manual SC 1000CP XT SC 1000CP XT Maintenance Manual