beautypg.com

SMA SC 500CP XT User Manual

Page 130

background image

Name

Description

Value/range

Explanation

Default
value

Q-VRtgOfsNom
**

Nominal voltage VRtg
of the voltage-dependent
reactive power control

This parameter is only ac-
tive if the parameter
Q‑VArMod is set to
VArCtlCol.

−10 % … +10 %

0 %

Q-VArGraNom
**

Reactive power gradient

0%/V to 40.06%/V

Sunny Central 500CP XT

0%/V

0%/V to 31.47%/V

Sunny Central 630CP XT

0%/V to 27.82%/V

Sunny Central 720CP XT

0%/V to 26.35%/V

Sunny Central 760CP XT

0%/V to 25.04%/V

Sunny Central 800CP XT

0%/V to 23.56%/V

Sunny Central 850CP XT

0%/V to 22.25%/V

Sunny Central 900CP XT

Q-VolWidNom
**

Voltage range

0 % … 20 %

0 %

Q-VolNomP1
**

Voltage at point 1

80 % … 120 %

100 %

Q-VolNomP2
**

Voltage at point 2

80 % … 120 %

100 %

Q-VArTmsSpnt
**

Time setting of the char-
acteristic curve point

0.2 s to 20 s

10 s

Q-VArTmsVtg
**

Connection delay of the
grid voltage

0.2 s to 20 s

10 s

Q-EnaTmsVtg
**

Activation of the connec-
tion delay of the grid
voltage

Off

Deactivated

Off

On

Activated

WGra**

Gradient of the active
power change for set-
point of active power lim-
itation

0.017%/s to 100%/
s

Country-
specific

WGraEna**

Activation of the active
power change gradient

Off

Deactivated

On

On

Activated

WGraRecon** Gradient of active power

change for reconnection

0.017%/s to 100%/
s

Country-
specific

WGraRe-
conEna**

Activation of the decou-
pling protection ramp for
reconnection

Off

Deactivated

Country-
specific

On

Activated

11 Operating Data and Parameters