SMA SC 500CP XT User Manual
Page 133
Name
Description
Value/range
Explanation
Default
value
Q-VLockInW** Voltage value from
which the Q(V) charac-
teristic curve is activated,
in % relative to the nomi-
nal voltage
0 % … 100 %
‒
0 %
Q-VLockOutW
**
Voltage value from
which the Q(V) charac-
teristic curve is deacti-
vated, in % based on the
nominal voltage
0 % … 100 %
‒
0 %
Q-VLockInTm
**
Waiting time for activa-
tion of the Q(V) charac-
teristic curve
0 s to 100 s
‒
2 s
Q-VLockOutTm
**
Waiting time for deacti-
vation of the Q(V) char-
acteristic curve
0 s to 100 s
‒
2 s
Q-
VArGraNomPo
s**
Reactive power gradient
at a positive change of
nominal voltage
0%/V to 40.06%/V
Sunny Central 500CP XT
0%/V
0%/V to 31.47%/V
Sunny Central 630CP XT
0%/V to 27.82%/V
Sunny Central 720CP XT
0%/V to 26.35%/V
Sunny Central 760CP XT
0%/V to 25.04%/V
Sunny Central 800CP XT
0%/V to 23.56%/V
Sunny Central 850CP XT
0%/V to 22.25%/V
Sunny Central 900CP XT
Q-
VArGraNomN
eg**
Reactive power gradient
at a negative change of
nominal voltage
0%/V to 40.06%/V
Sunny Central 500CP XT
0%/V
0%/V to 31.47%/V
Sunny Central 630CP XT
0%/V to 27.82%/V
Sunny Central 720CP XT
0%/V to 26.35%/V
Sunny Central 760CP XT
0%/V to 25.04%/V
Sunny Central 800CP XT
0%/V to 23.56%/V
Sunny Central 850CP XT
0%/V to 22.25%/V
Sunny Central 900CP XT
PF-
PFSubValRun
Substitute value cos φ in
normal feed-in operation
during communication
disturbance
The lower limit is defined
by the parameter PFAb-
sMin.
0.5 … 1
‒
1
11 Operating Data and Parameters
SMA Solar Technology AG
User Manual
133
SCCPXT-BA-E4-en-54
- SC 630CP XT SC 720CP XT SC 760CP XT SC 800CP XT SC 850CP XT SC 900CP XT SC 500CP XT Maintenance Manual SC 630CP XT Maintenance Manual SC 720CP XT Maintenance Manual SC 760CP XT Maintenance Manual SC 800CP XT Maintenance Manual SC 850CP XT Maintenance Manual SC 900CP XT Maintenance Manual SC 1000CP XT SC 1000CP XT Maintenance Manual