2 parameters, 1 inverter, 1 power limitation – SMA SC 500CP XT User Manual
Page 123: Inverter

11.2
Parameters
11.2.1 Inverter
11.2.1.1 Power Limitation
Name
Description
Value/range
Explanation
Default
value
Plimit*
Limitation of the nominal
device power including
apparent power
0 kW to 550 kW
Sunny Central 500CP XT
550 kW
0 kW to 700 kW
Sunny Central 630CP XT
700 kW
0 kW to 792 kW
Sunny Central 720CP XT
792 kW
0 kW to 836 kW
Sunny Central 760CP XT
836 kW
0 kW to 880 kW
Sunny Central 800CP XT
880 kW
0 kW to 935 kW
Sunny Central 850CP XT
935 kW
0 kW to 990 kW
Sunny Central 900CP XT
990 kW
Pmax**
Limitation of the nominal
power
0 kW to 550 kW
Sunny Central 500CP XT
550 kW
0 kW to 700 kW
Sunny Central 630CP XT
700 kW
0 kW to 792 kW
Sunny Central 720CP XT
792 kW
0 kW to 836 kW
Sunny Central 760CP XT
836 kW
0 kW to 880 kW
Sunny Central 800CP XT
880 kW
0 kW to 935 kW
Sunny Central 850CP XT
935 kW
0 kW to 990 kW
Sunny Central 900CP XT
990 kW
P-WMod**
Mode for active power
limitation
Off
Limits active power to Pmax
Off
WCtlCom
Limits active power via an exter-
nal control unit, such as the
Power Reducer Box
WCnst
Manually limits active power in
kW (P-W) via communication de-
vices, such as the SC-COM
WCnstNom
Manually limits active power in %
(P-WNom) via communication
devices, such as the SC-COM
WCnstNomAnIn
Limits active power in % at the
analog input
WCnstNomDigIn
Limits active power at the digital
input. This mode is not supported.
11 Operating Data and Parameters
SMA Solar Technology AG
User Manual
123
SCCPXT-BA-E4-en-54
- SC 630CP XT SC 720CP XT SC 760CP XT SC 800CP XT SC 850CP XT SC 900CP XT SC 500CP XT Maintenance Manual SC 630CP XT Maintenance Manual SC 720CP XT Maintenance Manual SC 760CP XT Maintenance Manual SC 800CP XT Maintenance Manual SC 850CP XT Maintenance Manual SC 900CP XT Maintenance Manual SC 1000CP XT SC 1000CP XT Maintenance Manual