SMA SC 500CP XT User Manual
Page 145

Name
Description
Value/range
Explanation
Default
value
DcCfg.AmpMax[4]
Maximum current of input
4
0 A to 500 A
‒
0 A
DcCfg.AmpMax[5]
Maximum current of input
5
0 A to 500 A
‒
0 A
DcCfg.AmpMax[6]
Maximum current of input
6
0 A to 500 A
‒
0 A
DcCfg.AmpMax[7]
Maximum current of input
7
0 A to 500 A
‒
0 A
DcCfg.AmpMax[8]
Maximum current of input
8
0 A to 500 A
‒
0 A
MaxTol
Tolerance in percent by
which the input current may
deviate from the mean
value
0.1% to 100 %
‒
4.0 %
DevFunc
Device function
---
Default, no action
---
ResetMeasuring
Restarts the algorithm. All
measured value are
deleted.
Factory
Resets all parameters to de-
fault settings
Ackn
Acknowledge errors
---
Default, no action
---
Quit
Acknowledgment of the
present error
AlarmEna
Activation of the error anal-
ysis
---
Default, no action
---
Off
No error analysis. Only
measured value are sent.
On
Error analysis activated. Er-
ror messages are gener-
ated, if deviations occur
(see Section 11.1.4.2,
page 122).
11 Operating Data and Parameters
SMA Solar Technology AG
User Manual
145
SCCPXT-BA-E4-en-54
- SC 630CP XT SC 720CP XT SC 760CP XT SC 800CP XT SC 850CP XT SC 900CP XT SC 500CP XT Maintenance Manual SC 630CP XT Maintenance Manual SC 720CP XT Maintenance Manual SC 760CP XT Maintenance Manual SC 800CP XT Maintenance Manual SC 850CP XT Maintenance Manual SC 900CP XT Maintenance Manual SC 1000CP XT SC 1000CP XT Maintenance Manual