beautypg.com

SMA SC 500CP XT User Manual

Page 142

background image

Name

Description

Value/range

Explanation

Default
value

MoniTmGr1On
*

Start time for monitoring of
group 1

07:00 a.m. to
7:00 p.m.

Parameter exists for all six
groups.

10:00 a.m.

MoniTmGr1Off
*

End time for monitoring of
group 1

07:00 a.m. to
7:00 p.m.

Parameter exists for all six
groups.

3:00 p.m.

MoniTmGrAl-
lOn*

Start time for monitoring of all
groups

07:00 a.m. to
7:00 p.m.

10:00 a.m.

MoniTmGrAl-
lOff*

End time for monitoring of all
groups

07:00 a.m. to
7:00 p.m.

3:00 p.m.

MoniTmComO
n*

Start time for monitoring of all
groups

07:00 a.m. to
7:00 p.m.

10:00 a.m.

MoniTmComOf
f*

End time for monitoring of all
groups

07:00 a.m. to
7:00 p.m.

3:00 p.m.

Ackn

Acknowledge errors

quit

ErrLevGr1*

Sensitivity of error detection for
group 1

Parameter exists for all six groups

24 Sensitive

50 min ‒ 10%

32 Regular

24 Regular

50 min ‒ 14%

24 Insensitive

50 min ‒ 18%

32 Sensitive

35 min ‒ 10%

32 Regular

35 min ‒ 13%

32 Insensitive

35 min ‒ 16%

64 Sensitive

15 min ‒ 7%

64 Regular

15 min ‒ 9%

64 Insensitive

15 min ‒ 10%

ComBaud*

Baud rate

1,200 baud

Parameter can only be
changed in the operating state
"Stop".

19,200
baud

4,800 baud

9,600 baud

19,200 baud

38,400 baud

57,600 baud

11 Operating Data and Parameters

SMA Solar Technology AG

User Manual

SCCPXT-BA-E4-en-54

142