SMA SC 500CP XT User Manual
Page 142

Name
Description
Value/range
Explanation
Default
value
MoniTmGr1On
*
Start time for monitoring of
group 1
07:00 a.m. to
7:00 p.m.
Parameter exists for all six
groups.
10:00 a.m.
MoniTmGr1Off
*
End time for monitoring of
group 1
07:00 a.m. to
7:00 p.m.
Parameter exists for all six
groups.
3:00 p.m.
MoniTmGrAl-
lOn*
Start time for monitoring of all
groups
07:00 a.m. to
7:00 p.m.
‒
10:00 a.m.
MoniTmGrAl-
lOff*
End time for monitoring of all
groups
07:00 a.m. to
7:00 p.m.
‒
3:00 p.m.
MoniTmComO
n*
Start time for monitoring of all
groups
07:00 a.m. to
7:00 p.m.
‒
10:00 a.m.
MoniTmComOf
f*
End time for monitoring of all
groups
07:00 a.m. to
7:00 p.m.
‒
3:00 p.m.
Ackn
Acknowledge errors
quit
‒
‒
ErrLevGr1*
Sensitivity of error detection for
group 1
Parameter exists for all six groups
24 Sensitive
50 min ‒ 10%
32 Regular
24 Regular
50 min ‒ 14%
24 Insensitive
50 min ‒ 18%
32 Sensitive
35 min ‒ 10%
32 Regular
35 min ‒ 13%
32 Insensitive
35 min ‒ 16%
64 Sensitive
15 min ‒ 7%
64 Regular
15 min ‒ 9%
64 Insensitive
15 min ‒ 10%
ComBaud*
Baud rate
1,200 baud
Parameter can only be
changed in the operating state
"Stop".
19,200
baud
4,800 baud
9,600 baud
19,200 baud
38,400 baud
57,600 baud
11 Operating Data and Parameters
SMA Solar Technology AG
User Manual
SCCPXT-BA-E4-en-54
142
- SC 630CP XT SC 720CP XT SC 760CP XT SC 800CP XT SC 850CP XT SC 900CP XT SC 500CP XT Maintenance Manual SC 630CP XT Maintenance Manual SC 720CP XT Maintenance Manual SC 760CP XT Maintenance Manual SC 800CP XT Maintenance Manual SC 850CP XT Maintenance Manual SC 900CP XT Maintenance Manual SC 1000CP XT SC 1000CP XT Maintenance Manual