beautypg.com

SMA SC 500CP XT User Manual

Page 118

background image

Errors and warnings relating to the reactive power setpoint

Name

Display

Description

Q-VArModFailStt

Off

No mode for specifying the reactive power setpoint has been se-
lected.

Ok

A mode for specifying the reactive power setpoint has been selected
and no error is present.

ComFail

The mode VArCtlCom or PFCtlCom has been selected and the ex-
pected signal with a valid reactive power setpoint has been absent
for at least five minutes.

AnInFail

The mode VArCnstNomAnIn or PFCnstAnIn has been selected
and the value measured at the analog input is less than 2 mA.

ComInvalid

The mode VArCtlCom or PFCtlCom has been selected and there is
invalid content in the power setpoint information.

Status messages of the reactive power setpoint

Name

Display

Description

Q-VArModStt

Off

No mode for specifying the reactive power setpoint has been se-
lected.

VdcMax

The reactive power is limited due to DC voltage being too high.

VacLimMax

The reactive power is limited due to AC voltage being too high.

VacLimMin

The reactive power is limited due to the AC voltage being too low.

SMaxVdcHigh

The maximum apparent power value is reduced. If the maximum DC
voltage increases, the reactive power is reduced.

SMax

The reactive power is limited by the maximum apparent power.

Tmp

The reactive power is limited by temperature derating.

AmpAC

The reactive power is limited via an AC current limitation.

P

The reactive power is limited due to the priority of the active power
setpoint.

FrtLim

The reactive power is limited due to the FRT voltage limit.

Displacement power factor and power setpoint

Name

Display

Description

PF

Current displacement power factor cos φ

PFExt

OvExt

Overexcited

UnExt

Underexcited

P-WSpt

Current power specification

11 Operating Data and Parameters

SMA Solar Technology AG

User Manual

SCCPXT-BA-E4-en-54

118