SMA SC 500CP XT User Manual

Page 131

background image

Name

Description

Value/range

Explanation

Default
value

P-VtgGraNom
**

Active power gradient
for voltage-dependent
active power limitation

0.017%/s to
100.000%/s

0.166%/s

P-VtgEna

Activation of voltage-de-
pendent active power
limitation

Off

Deactivated

Off

On

Activated

P-VtgNomP1

Voltage at point 1

100 % … 120 %

111%

P-VtgNomP2

Voltage at point 2

90 % … 120 %

110 %

P-VtgAtMin

Minimum active power
with voltage-dependent
active power limitation

0 % … 100 %

20 %

PwrApLimitPrio
***

Prioritization of reactive
power or active power

PrioPwrRtPrioPwrRt

Prioritization of reactive power

PrioPwrRtPri-
oPwrRt

PrioPwrAt

Prioritization of active power

SDLimComSrc
***

Selection of the SDLimit
source

CAN

Interface of the communication
unit

UART

UART

Via SMA Net

P-WSubVal

Substitute value for ac-
tive power limitation out-
side of normal feed-in
operation during commu-
nication disturbance

0 kW to 550 kW

Sunny Central 500CP XT

550 kW

0 kW to 700 kW

Sunny Central 630CP XT

700 kW

0 kW to 792 kW

Sunny Central 720CP XT

792 kW

0 kW to 836 kW

Sunny Central 760CP XT

836 kW

0 kW to 880 kW

Sunny Central 800CP XT

880 kW

0 kW to 935 kW

Sunny Central 850CP XT

935 kW

0 kW to 990 kW

Sunny Central 900CP XT

990 kW

P-WSubValRun

Substitute value for ac-
tive power limitation in
normal feed-in operation
during communication
disturbance

0 kW to 550 kW

Sunny Central 500CP XT

550 kW

0 kW to 700 kW

Sunny Central 630CP XT

700 kW

0 kW to 792 kW

Sunny Central 720CP XT

792 kW

0 kW to 836 kW

Sunny Central 760CP XT

836 kW

0 kW to 880 kW

Sunny Central 800CP XT

880 kW

0 kW to 935 kW

Sunny Central 850CP XT

935 kW

0 kW to 990 kW

Sunny Central 900CP XT

990 kW

11 Operating Data and Parameters

SMA Solar Technology AG

User Manual

131