background image

Name

Description

Value/range

Explanation

Default
value

DevFunc*

Manages the Sunny String-Moni-
tors

AutoDetect_
SSMU

Searches for all Sunny String-
Monitors and deletes previ-
ously detected Sunny String-
Monitors

0

DetectSSMU
Retry

Searches for undetected Sun-
ny String-Monitors only

DelAll_SSMU

Deletes all detected Sun-
ny String-Monitors

Factory

Resets all parameters to default
settings.

* To change these parameters, you must enter the installer password.

11.2.3 Sunny String-Monitor

Name

Description

Value/range

Explanation

Default
value

TMittelung*

Duration of averaging of current
measurements

0 s to 6,000 s

30 s

String Anzahl*

Number of detected strings

0 to 8

0

SW Version

Current firmware version

1 to 40

Value cannot be changed

SSM Identifier* Identification number of Sunny

String-Monitor

1 to 99

0

Group String 1
*

Assigns strings to their respective
group

0 to 3

Parameter exists for all eight
groups

0

Group String*

All groups

0 to 3

0

No.of String 1* Number of connected strings in

the respective group

1 to 4

Parameter exists for all eight
groups

If you wish to use this function,
contact us (see Section 13,
page 154).

No.of Strings*

All groups

1 to 4

Monitoring1
On*

Start of monitoring of strings in
group 1

0:00 a.m. to
11:59 p.m.

Parameter exists for all eight
groups

Configure the string settings
preferably via the Sunny Cen-
tral String-Monitor Controller.

0

Monitoring1
Off*

End of monitoring of strings in
group 1

0:00 a.m. to
11:59 p.m.

Parameter exists for all eight
groups

Configure the string settings
preferably via the Sunny Cen-
tral String-Monitor Controller.

0

11 Operating Data and Parameters

SMA Solar Technology AG

User Manual

143