11. Enter the data of your proxy server in the fields User name and Password.

12. Select the button [Save].

4.6.5

Detecting New Devices

During commissioning of a PV power plant, all devices must be detected. If multiple interfaces (e.g. COM2 and
COM3) are used in the inverter, detection of new devices must be carried out separately for all interfaces.

Devices will need to be redetected if you have:

• replaced devices in your PV power plant

• removed devices from your PV power plant

• added devices to your PV power plant

Detection of the PV power plant may take several minutes

Depending on the number of devices in your PV power plant, the duration of the detection process may vary.

• If there is no indication of progress on the communication unit after three minutes, cancel the search.

• Make sure the data cable of each device is properly connected and repeat the search.

Procedure:

1. Log into the user interface (see Section 9.4.1, page 81).

2. Select Data > Detection.

3. In the field Total number of devices to be detected, enter the number of devices connected to the

communication unit. Hint: If you do not know the number, enter 1.

4. Select the button [Start detection].

☑ The communication unit starts detecting all inverters and displays its progress. Once all devices have been

detected, the message ### Device detection finished ### is displayed.

5. Select the button [OK].

4.6.6

Setting the Power Limitation

4.6.6.1

Setting the Active Power Ramp-Up

Parameter block

Some parameters must only be changed in the operating state "Stop". The entry will not be accepted in any other
operating state.

The inverter works up to its maximum feed-in power via a ramp. This means that the inverter gradually increases the
ratio of feed-in power per second by the value set in the parameter WGra.

Procedure:

1. Make sure the inverter is in the operating state "Stop".

2. Call up the parameter overview (see Section 9.3.1, page 81).

3. Set the parameter WGra to the required value.

4. Save the parameter changes (see Section 9.3.2, page 81).

4.6.6.2

Setting the Frequency-Dependent Active Power Limitation

Parameter block

Some parameters must only be changed in the operating state "Stop". The entry will not be accepted in any other
operating state.