Procedure:

1. Log into the user interface (see Section 9.4.1, page 81).

2. Select the instantaneous value P-WModFailStt.

Display

Cause and corrective measures

Off

No mode for active power limitation has been selected.

OK

A mode for active power limitation has been selected and no error is present.

ComFail

The mode WCtlCom has been selected and the expected signal with a valid active
power limitation has been absent for at least five minutes.

Corrective measures:

• Ensure that the communication units can be accessed via the Internet.

• Ensure that the communication units are connected correctly.

• Ensure that the cabling between the communication units is ok.

AnInFail

The mode WCnstNomAnIn has been selected and the value measured at the analog in-
put is less than 2 mA.

Corrective measures:

• Make sure the cable is correctly connected to the analog input.

ComInvalid

The mode WCtlCom has been selected and there is invalid content in the power setpoint
information.

Corrective measures:

• Check the power specification settings.

7.5.7

Displaying Disturbance Messages for the Reactive Power Setpoint

The instantaneous value Q‑VArModFailStt displays errors or warnings relating to the reactive power setpoint.

Procedure:

1. Log into the user interface (see Section 9.4.1, page 81).

2. Select the instantaneous value Q-VArModFailStt.

Display

Cause and corrective measure

Off

No mode for specifying the reactive power setpoint has been selected.

OK

A mode for specifying the reactive power setpoint has been selected and no error is
present.

ComFail

The mode VArCtlCom or PFCtlCom has been selected and the expected signal with a
valid reactive power setpoint has been absent for at least five minutes.

Corrective measures:

• Ensure that the communication units can be accessed via the Internet.

• Ensure that the communication units are connected correctly.

• Ensure that the cabling between the communication units is ok.

7 Troubleshooting

SMA Solar Technology AG

User Manual

SCCPXT-BA-E4-en-54

76