4.6.9
Setting Project-Specific Parameters
4.6.9.1
Setting the Remote Shutdown
1. Call up the parameter overview (see Section 9.3.1, page 81).
2. To activate remote shutdown, set the parameter ExlStrStpEna to On (see Section 10.2.1.2, page 88).
3. To deactivate remote shutdown, set the parameter ExlStrStpEna to Off (see Section 10.2.1.2, page 88).
4. Save the parameter changes (see Section 9.3.2, page 81).
4.6.9.2
Deactivating the "Fully Hermetic" Transformer Protection
1. Call up the parameter overview (see Section 9.3.1, page 81).
2. Set the parameter ExlTrfErrEna to Off (see Section 10.2.2.2 "Transformer Protection", page 88)
3. Save the parameter changes (see Section 9.3.2, page 81).
4.6.10 Setting the String Current Monitoring
4.6.10.1 Detecting the Sunny Central String-Monitor Controller and the Inverter
1. Log into the user interface (see Section 9.4.1, page 81).
2. Select Data > Detection.
3. In the field Total number of devices to be detected, enter the value 2.
4. Select the button [Start detection].
☑ The communication unit starts detecting all inverters and displays its progress. Once all devices have been
detected, the message ### Device detection finished ### is displayed.
☑ The devices have been detected.
4.6.10.2 Setting the Date and Time of the Sunny Central String-Monitor Controller
1. Log into the user interface (see Section 9.4.1, page 81).
2. Select Data > Devices.
3. Select
.
☑ A list of the existing device types appears.
4. Select Sunny Central String-Monitor Controller.
5. Select the tab Instantaneous values.
6. Make sure that the date SysDt and time SysTm of the Sunny Central String-Monitor Controller are correct.
If the settings are incorrect, change the parameters Dt and Tm .
4.6.10.3 Detecting the Sunny String-Monitors via the Sunny Central String-
Monitor Controller
It may take several minutes to detect the Sunny String-Monitors, depending on the number of devices and how far
apart they are.
Procedure:
1. Log into the user interface (see Section 9.4.1, page 81).
2. Select the tab Parameters.
3. Set the parameter DevFunc to AutoDetect_SSMU.
4. Select the button [Save].
4 Commissioning
SMA Solar Technology AG
User Manual
SCCPXT-BA-E4-en-54
42
- SC 630CP XT SC 720CP XT SC 760CP XT SC 800CP XT SC 850CP XT SC 900CP XT SC 500CP XT Maintenance Manual SC 630CP XT Maintenance Manual SC 720CP XT Maintenance Manual SC 760CP XT Maintenance Manual SC 800CP XT Maintenance Manual SC 850CP XT Maintenance Manual SC 900CP XT Maintenance Manual SC 1000CP XT SC 1000CP XT Maintenance Manual