Error no. Explanation

Inverter behavior

Corrective measures

S1

S2

R

0404*

Frequency change per second too
high for grid operation

30 s

30 s

0502*

Power frequency is too low. Power
frequency disturbance detected by
standard monitoring.

30 s

30 s

• Check power frequency.

• Check the display of the grid monitoring

relay.

• Make sure the fuses in the load circuit

function properly.

0503*

Power frequency is too high.
Power frequency disturbance de-
tected by standard monitoring.

30 s

30 s

0504*

Power frequency is too low. Power
frequency disturbance detected by
redundant monitoring.

30 s

30 s

0505*

Power frequency is too high.
Power frequency disturbance de-
tected by redundant monitoring.

30 s

30 s

0506*

The inverter has detected a stand-
alone grid and has disconnected
from the utility grid.

W

W

• Check power frequency.

0801*

One line conductor of the utility
grid has failed.

30 s

30 s

• Check the grid voltage.

• Make sure the external fuses work

properly.

• Make sure the AC cable connections

are tight.

0802*

1301

Left-hand rotating magnetic field is
connected.

30 s

Q

• Check phase position.

• Make sure all fuses are switched on.

1500

The conditions for grid reconnec-
tion have not yet been reached af-
ter a grid error.

W

W

• Check the power frequency and grid

voltage.

* Depending on the parameterization, the disturbance message may have to be acknowledged manually.

7.5.4

Error Numbers 34xx to 40xx - Disturbance on the PV Array

Error no. Explanation

Inverter behavior

Corrective measures

S1

S2

R

3403

PV array voltage is too high.

15
min

30
min

• Check the DC voltage.

• Check the module wiring and system

design.

3404

Open-circuit voltage is too high.
Disturbance detected by standard
monitoring.

15
min

30
min

3406

DC voltage is too high.

15
min

30
min

7 Troubleshooting

SMA Solar Technology AG

User Manual

SCCPXT-BA-E4-en-54