Error no. Explanation

Inverter behavior

Corrective measures

S1

S2

R

6441

Sensor error during measurement
of DC voltage

30 s

30 s

• Contact SMA Service Line.

6443

Unspecified error in digital signal
processor

30 s

x

• Contact SMA Service Line.

6447

Self-test of inverter bridge failed

Q

Q

• Contact SMA Service Line.

6448

Insulation monitoring provides non-
permitted values

W

W

• Check insulation monitoring.

6451

Measured AC voltage of the in-
verter is less than utility grid volt-
age.

W

W

• Contact SMA Service Line.

6452

Measured AC voltage of the utility
grid is less than inverter voltage.

W

W

• Contact SMA Service Line.

6453

AC voltage of grid limit monitoring
is faulty.

W

W

• Contact SMA Service Line.

6454

AC current is faulty.

W

W

• Contact SMA Service Line.

6455

AC voltage is faulty.

W

W

• Contact SMA Service Line.

6456

Pre-charging circuit of DC link is
defective.

W

W

• Contact SMA Service Line.

6457

Capacitor self-test has failed.

Q

Q

• Contact SMA Service Line.

6461

Insulation monitoring device has
not adopted threshold.

15
min

15
min

x

• Check the insulation monitoring device

and cabling.

6471

Online capacitor self-test has
failed.

Q

Q

x

• Contact SMA Service Line.

6472

Endless loop between online and
offline capacitor test

Q

Q

x

• Contact SMA Service Line.

6501

Interior temperature of inverter is
too high.

30 s

1 min

• Check function of the fans.

• Clean the fans.

• Clean clogged fan inlets and ventilation

plates.

6502

Temperature of inverter bridge is
too high.

30 s

1 min

6508

Outside temperature is too high.

30 s

1 min

6605

The fast stop was tripped due
overtemperature in the switch cabi-
net.

30 s

1 min

• Contact SMA Service Line.

7 Troubleshooting

SMA Solar Technology AG

User Manual

73

SCCPXT-BA-E4-en-54