3 visual inspection and mechanical test, Visual inspection and mechanical test, Sequence for visual inspection and mechanical test – SMA SC 500CP XT User Manual
Page 29
☐ All doors and locks must function properly.
☐ All documentation must be available.
☐ All labels must be in place.
4.3
Visual Inspection and Mechanical Test
4.3.1
Sequence for Visual Inspection and Mechanical Test
Procedure
See
1.
Ensure that the minimum clearances are complied with.
2.
Ensure that the grounding busbar has been professionally connected to the external grounding system.
3.
Ensure that the cables for communication, control, supply voltage and
monitoring are correctly connected.
4.
Ensure that the high-current contacts made on the installation site are cor-
rectly connected.
5.
Ensure that the high-current contacts made at the factory are correctly
connected.
6.
Ensure that the connection busbars do not show any discoloration.
If the connection busbars show any discoloration, please contact us (see Section 13 "Contact", page 154).
7.
Ensure that the settings of the switching units are made correctly.
8.
Ensure that all connectors are correctly connected.
4.3.2
Checking the Connections of the Cables for Communication, Control
Supply Voltage and Monitoring
Test Point
Tasks
Cables
Ensure that the cable type and cross-section, the number of cables and the labeling comply
with the specifications in the schematic diagram.
Cable connection
Ensure that the cable connection complies with the specifications in the schematic diagram.
If no external fast stop is to be installed, ensure that the terminals are wired with a jumper
wire in accordance with the schematic diagram.
Cable insulation
Make sure that the insulation of the cables is correctly stripped. The insulation must not pre-
vent the contact with the terminal.
Bootlace ferrules
Ensure that the bootlace ferrules are correctly crimped and that no stranded wires are visible.
Cable support rails
Ensure that the cables are adequately attached to the cable support rails.
Shield clamping sad-
dles
Ensure that the contact between the cable shield and the shield bus is intact.
4 Commissioning
SMA Solar Technology AG
User Manual
29
SCCPXT-BA-E4-en-54
- SC 630CP XT SC 720CP XT SC 760CP XT SC 800CP XT SC 850CP XT SC 900CP XT SC 500CP XT Maintenance Manual SC 630CP XT Maintenance Manual SC 720CP XT Maintenance Manual SC 760CP XT Maintenance Manual SC 800CP XT Maintenance Manual SC 850CP XT Maintenance Manual SC 900CP XT Maintenance Manual SC 1000CP XT SC 1000CP XT Maintenance Manual