Explanation of the Error Tables

You will find the following information in the error tables in the following sections:

1301

3803

0104

Error no.

Grid voltage is too high.

DC current of PV array is too high.

Left-hand rotating magnetic field
is connected.

Explanation

W

1 min

30 s

S1

C

D

Q

S2

x

R

Corrective measures

• Check phase position.

• Check DC input current.

• Check grid voltage.

A

B

Position

Explanation

A

Behavior of the inverter: disturbance level S1, disturbance level S2

• s / min: waiting time

• C: system-specific

• D: day change

• Q: waiting for acknowledgement

• W: warning

B

Reset

7.5.3

Error Numbers 01xx to 13xx - Disturbance on the Utility Grid

After a grid failure, the inverter monitors the utility grid for a specific period before reconnecting. When the inverter
monitors the utility grid after a grid error, the grid monitoring time is complied with. Certain errors, such as grid errors,
cause the inverter to shut down. In this case, the instantaneous value TmsRmg indicates the time for which the inverter
monitors the utility grid before reconnecting. This grid monitoring time can be defined in parameter GdErrTm.

Error no. Explanation

Inverter behavior

Corrective measures

S1

S2

R

0103*

Grid voltage is too high. Overvolt-
age detected by redundant moni-
toring.

30 s

30 s

• Check the grid voltage.

• Check grid connections.

• Check stability of the utility grid.

• Make sure the external fuses work

properly.

• Make sure the AC cable connections

are tight.

0104*

Grid voltage is too high. Overvolt-
age detected by standard monitor-
ing.

C

C

0203*

Grid voltage is too low. Undervolt-
age detected by redundant moni-
toring.

30 s

30 s

0204*

Grid voltage is too low. Undervolt-
age detected by standard monitor-
ing.

30 s

30 s

0205*

Grid synchronization not possible

30 s

30 s

7 Troubleshooting

SMA Solar Technology AG

User Manual

69

SCCPXT-BA-E4-en-54