5 project-specific parameters – SMA SC 500CP XT User Manual

Page 139

background image

Name

Description

Value/range

Explanation

Default
value

IsoDev*

Selection of insulation
monitoring device

isoPV3

isoPV3

isoPV1685

* To view or change this parameter, you must enter the installer password.

11.2.1.5 Project-Specific Parameters

Name

Description

Value/range

Explanation

Default
value

PvPwrMinTr

Threshold for starting the
MPP tracker

0 kW to 20 kW

20 kW

PvPwrMinTrT

Timeout for starting the
MPP tracker

1 s to 1,800 s

600 s

PvVtgStrLevMin
*

Threshold for switching
to feed-in operation

0 V to 1,200 V

Sunny Central 500CP XT

500 V

0 V to 1,200 V

Sunny Central 630CP XT

610 V

0 V to 1,200 V

Sunny Central 720CP XT

630 V

0 V to 1,200 V

Sunny Central 760CP XT

660 V

0 V to 1,200 V

Sunny Central 800CP XT

705 V

0 V to 1,200 V

Sunny Central 850CP XT

760 V

0 V to 1,200 V

Sunny Central 900CP XT

770 V

PVStrT

Once the specified time
has elapsed, the inverter
switches from the operat-
ing state "Grid monitor-
ing" to the operating
state "Grid monitoring
time reached".

1 s to 300 s

90 s

VArGra**

Gradient of reactive
power change

0%/s to 200%/s

20%/s

QoDInvCurPv
***

Maximum allowed re-
verse current to the PV
array

−1,600 A to 0 A

−60 A

MppFact

Ratio between maximum
power P

MPP

of the PV cell

at the maximum power
point and the product of
open-circuit voltage V

OC

and short-circuit current I

SC

0.5 … 1

0.8

Serial Number
***

Inverter serial number

0 … 2147483647

0

11 Operating Data and Parameters

SMA Solar Technology AG

User Manual

139