5 project-specific parameters – SMA SC 500CP XT User Manual
Page 139

Name
Description
Value/range
Explanation
Default
value
IsoDev*
Selection of insulation
monitoring device
isoPV3
‒
isoPV3
isoPV1685
‒
* To view or change this parameter, you must enter the installer password.
11.2.1.5 Project-Specific Parameters
Name
Description
Value/range
Explanation
Default
value
PvPwrMinTr
Threshold for starting the
MPP tracker
0 kW to 20 kW
‒
20 kW
PvPwrMinTrT
Timeout for starting the
MPP tracker
1 s to 1,800 s
‒
600 s
PvVtgStrLevMin
*
Threshold for switching
to feed-in operation
0 V to 1,200 V
Sunny Central 500CP XT
500 V
0 V to 1,200 V
Sunny Central 630CP XT
610 V
0 V to 1,200 V
Sunny Central 720CP XT
630 V
0 V to 1,200 V
Sunny Central 760CP XT
660 V
0 V to 1,200 V
Sunny Central 800CP XT
705 V
0 V to 1,200 V
Sunny Central 850CP XT
760 V
0 V to 1,200 V
Sunny Central 900CP XT
770 V
PVStrT
Once the specified time
has elapsed, the inverter
switches from the operat-
ing state "Grid monitor-
ing" to the operating
state "Grid monitoring
time reached".
1 s to 300 s
‒
90 s
VArGra**
Gradient of reactive
power change
0%/s to 200%/s
‒
20%/s
QoDInvCurPv
***
Maximum allowed re-
verse current to the PV
array
−1,600 A to 0 A
‒
−60 A
MppFact
Ratio between maximum
power P
MPP
of the PV cell
at the maximum power
point and the product of
open-circuit voltage V
OC
and short-circuit current I
SC
0.5 … 1
‒
0.8
Serial Number
***
Inverter serial number
0 … 2147483647
‒
0
11 Operating Data and Parameters
SMA Solar Technology AG
User Manual
139
SCCPXT-BA-E4-en-54
- SC 630CP XT SC 720CP XT SC 760CP XT SC 800CP XT SC 850CP XT SC 900CP XT SC 500CP XT Maintenance Manual SC 630CP XT Maintenance Manual SC 720CP XT Maintenance Manual SC 760CP XT Maintenance Manual SC 800CP XT Maintenance Manual SC 850CP XT Maintenance Manual SC 900CP XT Maintenance Manual SC 1000CP XT SC 1000CP XT Maintenance Manual