Name
Description
Value/range
Explanation
Default
value
Qmax**
Limitation of reactive
power
0 kVAr to 245 kVAr
Sunny Central 500CP XT
245 kVAr
0 kVAr to 310 kVAr
Sunny Central 630CP XT
310 kVAr
0 kVAr to 346 kVAr
Sunny Central 720CP XT
346 kVAr
0 kVAr to 365 kVAr
Sunny Central 760CP XT
365 kVAr
0 kVAr to 385 kVAr
Sunny Central 800CP XT
385 kVAr
0 kVAr to 409 kVAr
Sunny Central 850CP XT
409 kVAr
0 kVAr to 433 kVAr
Sunny Central 900CP XT
433 kVAr
QoDQmax*
Limitation of reactive
power in the operating
state "Q at Night".
The reactive power can-
not exceed Qlimit.
0 kVAr to 245 kVAr
Sunny Central 500CP XT
245 kVAr
0 kVAr to 310 kVAr
Sunny Central 630CP XT
310 kVAr
0 kVAr to 346 kVAr
Sunny Central 720CP XT
346 kVAr
0 kVAr to 365 kVAr
Sunny Central 760CP XT
365 kVAr
0 kVAr to 385 kVAr
Sunny Central 800CP XT
385 kVAr
0 kVAr to 409 kVAr
Sunny Central 850CP XT
409 kVAr
0 kVAr to 433 kVAr
Sunny Central 900CP XT
433 kVAr
QEnsure*
Guaranteed reactive
power
0 kVAr to 550 kVAr
Sunny Central 500CP XT
0 kVAr
0 kVAr to 700 kVAr
Sunny Central 630CP XT
0 kVAr to 792 kVAr
Sunny Central 720CP XT
0 kVAr to 836 kVAr
Sunny Central 760CP XT
0 kVAr to 880 kVAr
Sunny Central 800CP XT
0 kVAr to 935 kVAr
Sunny Central 850CP XT
0 kVAr to 990 kVAr
Sunny Central 900CP XT
PFAbsMin*
Limitation of the displace-
ment power factor cos φ
0.5 … 1
‒
0.9
11 Operating Data and Parameters
SMA Solar Technology AG
User Manual
125
SCCPXT-BA-E4-en-54
- SC 630CP XT SC 720CP XT SC 760CP XT SC 800CP XT SC 850CP XT SC 900CP XT SC 500CP XT Maintenance Manual SC 630CP XT Maintenance Manual SC 720CP XT Maintenance Manual SC 760CP XT Maintenance Manual SC 800CP XT Maintenance Manual SC 850CP XT Maintenance Manual SC 900CP XT Maintenance Manual SC 1000CP XT SC 1000CP XT Maintenance Manual