beautypg.com

SMA SC 500CP XT User Manual

Page 125

background image

Name

Description

Value/range

Explanation

Default
value

Qmax**

Limitation of reactive
power

0 kVAr to 245 kVAr

Sunny Central 500CP XT

245 kVAr

0 kVAr to 310 kVAr

Sunny Central 630CP XT

310 kVAr

0 kVAr to 346 kVAr

Sunny Central 720CP XT

346 kVAr

0 kVAr to 365 kVAr

Sunny Central 760CP XT

365 kVAr

0 kVAr to 385 kVAr

Sunny Central 800CP XT

385 kVAr

0 kVAr to 409 kVAr

Sunny Central 850CP XT

409 kVAr

0 kVAr to 433 kVAr

Sunny Central 900CP XT

433 kVAr

QoDQmax*

Limitation of reactive
power in the operating
state "Q at Night".

The reactive power can-
not exceed Qlimit.

0 kVAr to 245 kVAr

Sunny Central 500CP XT

245 kVAr

0 kVAr to 310 kVAr

Sunny Central 630CP XT

310 kVAr

0 kVAr to 346 kVAr

Sunny Central 720CP XT

346 kVAr

0 kVAr to 365 kVAr

Sunny Central 760CP XT

365 kVAr

0 kVAr to 385 kVAr

Sunny Central 800CP XT

385 kVAr

0 kVAr to 409 kVAr

Sunny Central 850CP XT

409 kVAr

0 kVAr to 433 kVAr

Sunny Central 900CP XT

433 kVAr

QEnsure*

Guaranteed reactive
power

0 kVAr to 550 kVAr

Sunny Central 500CP XT

0 kVAr

0 kVAr to 700 kVAr

Sunny Central 630CP XT

0 kVAr to 792 kVAr

Sunny Central 720CP XT

0 kVAr to 836 kVAr

Sunny Central 760CP XT

0 kVAr to 880 kVAr

Sunny Central 800CP XT

0 kVAr to 935 kVAr

Sunny Central 850CP XT

0 kVAr to 990 kVAr

Sunny Central 900CP XT

PFAbsMin*

Limitation of the displace-
ment power factor cos φ

0.5 … 1

0.9

11 Operating Data and Parameters

SMA Solar Technology AG

User Manual

125

SCCPXT-BA-E4-en-54