SMA SC 500CP XT User Manual
Page 77
Display
Cause and corrective measure
AnInFail
The mode VArCnstNomAnIn or PFCnstAnIn has been selected and the value mea-
sured at the analog input is less than 2 mA.
Corrective measures:
• Make sure the cable is correctly connected to the analog input.
ComInvalid
The mode VArCtlCom or PFCtlCom has been selected and there is invalid content in
the power setpoint information.
Corrective measures:
• Check the power specification settings.
7 Troubleshooting
SMA Solar Technology AG
User Manual
77
SCCPXT-BA-E4-en-54
This manual is related to the following products:
- SC 630CP XT SC 720CP XT SC 760CP XT SC 800CP XT SC 850CP XT SC 900CP XT SC 500CP XT Maintenance Manual SC 630CP XT Maintenance Manual SC 720CP XT Maintenance Manual SC 760CP XT Maintenance Manual SC 800CP XT Maintenance Manual SC 850CP XT Maintenance Manual SC 900CP XT Maintenance Manual SC 1000CP XT SC 1000CP XT Maintenance Manual