Error no. Explanation

Inverter behavior

Corrective measures

S1

S2

R

7801

The surge arrester is defective or
the back-up fuse of the surge ar-
rester was tripped.

W

W

• Check the surge arrester.

• Check the back-up fuse of the surge

arrester.

7901

Reverse current has occurred in PV
array.

1 min

D

x

• Contact SMA Service Line.

8004

The inverter starts to derate due to
overcurrent at the DC switchgear
(SMID).

W

W

8701

External active power setpoints
are smaller than 2 mA and there-
fore invalid. The last valid value or,
after a day change, Pmax is
used. Once valid setpoints are
available again, these will be
used.

W

W

• Contact SMA Service Line.

8702

Several digital active power set-
points are available.

W

W

• Contact SMA Service Line.

8703

Power factor of the external reac-
tive power setpoint is invalid.

W

W

• Contact SMA Service Line.

8704

External active and reactive power
setpoints are invalid.

W

W

• Contact SMA Service Line.

9000

Power electronics self-test is run-
ning. This message disappears
once the self-test is complete.

W

W

9008

Doors have been opened during
operation.

30 s

1 min

• Contact SMA Service Line.

9009

Fast stop was manually tripped.

30 s

30 s

• Eliminate error and switch fast stop back

on.

9013

This relates to a grid management
shutdown. The error is reset by a
signal from the grid operator or
from the safety system of the grid
interconnection point.

30 s

30 s

• Eliminate error and switch fast stop back

on.

9019

Defective fast stop

30 s

C

• Check the fast stop cabling.