2 reconnecting the ac side, 3 reconnecting the dc side, 4 restarting the inverter – SMA SC 500CP XT User Manual
Page 54: Reconnecting the ac side, Reconnecting the dc side, Restarting the inverter
5. If the supply voltage has been disconnected upstream from the
circuit breaker, switch the circuit breaker of the supply voltage
on.
5.3.2
Reconnecting the AC Side
1. Reconnect the supply voltage and external voltages (see Section 5.3.1, page 53).
2. Reconnect the AC voltage of the MV transformer.
3. Switch on the AC disconnection unit in the inverter.
5.3.3
Reconnecting the DC Side
1. Insert all fuses and disconnection blades into all fuse holders of the inverter. Use an LV/HRC fuse extractor.
2. Mount the protective covers over the fuses (see Section 9.1.2, page 80).
3. Switch on the DC voltage in the DC main distribution or DC subdistribution (see documentation of the main or
subdistribution).
5.3.4
Restarting the Inverter
• Turn the key switch to Start.
5 Disconnecting and Reconnecting
SMA Solar Technology AG
User Manual
SCCPXT-BA-E4-en-54
54
- SC 630CP XT SC 720CP XT SC 760CP XT SC 800CP XT SC 850CP XT SC 900CP XT SC 500CP XT Maintenance Manual SC 630CP XT Maintenance Manual SC 720CP XT Maintenance Manual SC 760CP XT Maintenance Manual SC 800CP XT Maintenance Manual SC 850CP XT Maintenance Manual SC 900CP XT Maintenance Manual SC 1000CP XT SC 1000CP XT Maintenance Manual