beautypg.com

SMA SC 500CP XT User Manual

Page 135

background image

Name

Description

Range

Explanation

Default
value

VCtllLim

Threshold for undervolt-
age release level 1

0 % … 100 %

Country-
specific

VCtllLimTm

Delay time for undervolt-
age level 1

0 ms -
to 1,000,000 ms

Country-
specific

VCtlllLim

Threshold for undervolt-
age release level 2

0 % … 100 %

Country-
specific

VCtlllLimTm

Delay time for undervolt-
age level 2

0 ms -
to 1,000,000 ms

Country-
specific

VCtlMin

Threshold for undervolt-
age release level 3

0 % … 100 %

Country-
specific

VCtlMinTm

Delay time for undervolt-
age level 3

0 ms -
to 1,000,000 ms

Country-
specific

VCtllCharEna

Activation of dynamic un-
dervoltage detection

Off

Deactivated

Country-
specific

On

Activated

VCtllCharTm

Start time of dynamic un-
dervoltage detection

0 ms to
1,000,000 ms

77 ms

VCtlOpMinNo
m

Minimum connection
voltage

0 % … 100 %

Country-
specific

VCtlOpMaxNo
m

Maximum connection
voltage

100 % … 200 %

Country-
specific

HzCtlOpMin

Minimum connection fre-
quency

Country-specific

Country-
specific

HzCtlOpMax

Maximum connection fre-
quency

Country-specific

Country-
specific

HzCtlOpMaxR
econ

Maximum connection fre-
quency after grid error

Country-specific

Country-
specific

HzCtlMax

Threshold for overfre-
quency level 3

Country-specific

Country-
specific

HzCtlMaxTm

Delay time for overfre-
quency level 3

0 ms to 1,000,000
ms

Country-
specific

HzCtlhhLim

Threshold for overfre-
quency level 2

Country-specific

Country-
specific

HzCtlhhLimTm

Delay time for overfre-
quency level 2

0 ms -
to 1,000,000 ms

Country-
specific

HzCtlhLim

Threshold for overfre-
quency level 1

Country-specific

Country-
specific

HzCtlhLimTm

Delay time for overfre-
quency level 1

0 ms -
to 1,000,000 ms

Country-
specific

11 Operating Data and Parameters

SMA Solar Technology AG

User Manual

135

SCCPXT-BA-E4-en-54