11 Operating Data and Parameters

11.1

Operating Data

11.1.1 Inverter

11.1.1.1 Power Limitation

Errors and warnings relating to active power limitation

Name

Display

Description

P-WModFailStt

Off

No mode for active power limitation has been selected.

Ok

A mode for active power limitation has been selected and no error is
present.

ComFail

The mode WCtlCom has been selected and the expected signal with
a valid active power limitation has been absent for at least five min-
utes.

AnInFail

The mode WCnstNomAnIn has been selected and the value mea-
sured at the analog input is less than 2 mA.

ComInvalid

The mode WCtlCom has been selected and there is invalid content
in the power setpoint information.

Status messages of active power limitation

Name

Display

Description

P-WModStt

Off

No mode for active power limitation has been selected.

WMax

Active power is limited by specification of an upper limit. This limit is
based on Pmax.

Hz

Active power is limited by a frequency increase.

Tmp

Active power is limited by temperature derating.

AmpPv

Active power is limited via a PV current limitation.

AmpAC

Active power is limited via an AC current limitation.

SMax

The active power is limited by the maximum apparent power.

Q-VAr

The active power is limited due to the priority of the reactive power
setpoint.

QEnsure

The active power is limited due to the intermediate storage of reac-
tive power.

P-Vtg

The active power is limited due to the characteristic curve P(V).

VdcMax

The active power is increased via the setpoint due to the DC voltage
being too high.

AmpPvOptiprot

For the order option "Optiprotect", the active power is limited due to
switch currents being too high.