GASBOY Series 1000
2-22
03/07/03
Pulse Rates
Description
The Series 1000 System can accept pulse rates of dollar (one pulse per penny);
and quantity (1:1, 10:1, 100:1, 250:1, 500:1, and 1000:1 ratios). Pulse rates may
differ between pumps and the pulse rate definitions are loaded into the system via
the data terminal. The pulse rate switch is located in the system cabinet in an
area sealable by Weights and Measures for retail applications. When the switch
is set to enabled, no transactions can occur at the system and the message
REMOTE CONFIGURATION appears on the display.
Activate/Inactivate a Pump Via Terminal
Activate Pump
This feature allows the system operator to use the AP command to activate a
pump (hose) from a data terminal for one transaction. This transaction is
recorded as a normal transaction except that the digits of information, which
would normally be read off the card, are recorded as all 9’s (See Figure 2-13).
VT7PÂ Â97T@Â AIRÂÂ
XADÂÂ @7VAÂ
VEIAÂÂ RÆÂ
RT SW7PVEVa Q@QIÂ
ATTQTÂ
!&$Â Â))))Â ))))Â
))))Â #"")"Â !!0% Â !Â
!  ! "  Â
Figure 2-13. Transaction Activated via Terminal
Inactivate Pump
The system operator can turn off any pump (hose), currently in use, from a data
terminal by using the IP command. The pump is inactivated only for that
transaction and the message TTY CMD is placed in the ERROR field for that
transaction.
Pump Enable and Disable Via Terminal
Through a data terminal, the system operator can enable (EP) or disable a pump
(DP) from further use. With the DP command. a PUMP DISABLED notation
appears for that pump in the pump status (PP command) printout. The pump
remains disabled until the system operator re-enables it through the data terminal.
Automatic Pump Disable
As a safeguard against defective pulse transmitters in the pumps, the system
operator may configure the system to automatically disable a pump after a
number (1-99) of consecutive no quantity transactions. If a pump becomes
disabled in this manner, a PUMP # X DISABLED message appears on the direct
printout. The pump remains disabled until the system operator re-enables it
through the data terminal.
Automatic Site Shutdown Via Terminal
The system operator can set a time period each day when the system is
automatically shut down and all users are denied access to the fuel dispensing
equipment. A SITE IS DOWN message appears on the system’s LCD display.