beautypg.com

6 others, 1 speed limit, 2 torque limit – Delta Electronics AC Servo Drive ASDA-B User Manual

Page 146: 6 others -31, 1 speed, Limit -31, 2 torque limit -31, 6 others 6.6.1 speed limit

background image

Chapter 6 Control Modes of Operation|ASDA-B Series

Revision February 2008, Doc. Name: 2006PDD23000009

6-31

6.6 Others

6.6.1 Speed Limit

The max. servo motor speed can be limited by using parameter P1-55 no matter in position, speed or

torque control mode.

The command source of speed limit command is the same as speed command. It can be the external

analog voltage but also can be internal parameters (P1-09 to P1-11). For more information of speed

command source, please refer to chapter 6.3.1.

The speed limit only can be used in torque mode (T mode) to limit the servo motor speed. When the

torque command is the external analog voltage, there should be surplus DI signal that can be treated as

SPD0~1 and be used to select speed limit command (internal parameter). If there is not enough DI

signal, the external voltage input can be used as speed limit command. When the Disable / Enable

Speed Limit Function Settings in parameter P1-02 is set to 1, the speed limit function is activated.

The timing chart of speed limit is shown as the figure below:

Disable / Enable Speed Limit Function

Settings in parameter P1-02 is set to 1

SPD0~1 INVALID

SPD0~1 VALID

Disable / Enable Speed Limit Function

Settings in parameter P1-02 is set to 0

Command Source Selection of Speed Limit

6.6.2 Torque Limit

The command source of torque limit command is the same as torque command. It can be the external

analog voltage but also can be internal parameters (P1-12 to P1-14). For more information of torque

command source, please refer to chapter 6.4.1.

The torque limit only can be used in position mode (P mode) and speed mode (S mode) to limit the

output torque of servo motor. When the position command is the external pulse and speed command is

the external analog voltage, there should be surplus DI signal that can be treated as TCM0~1 used to

select torque limit command (internal parameter). If there is not enough DI signal, the external voltage

input can be used as torque limit command. When the Disable / Enable Torque Limit Function Settings

in parameter P1-02 is set to 1, the torque limit function is activated.

The timing chart of torque limit is shown as the figure below:

TCM0~1 INVALID

TCM0~1 VALID

Disable / Enable Torque Limit Function

Settings in parameter P1-02 is set to 1

Disable / Enable Torque Limit Function

Settings in parameter P1-02 is set to 0

Command Source Selection of Torque Limit