Basler Electric BE1-700 User Manual
Page 351

Manual Change - Mode 1
Manual Change Mode 1 test procedures are a continuation of the automatic test procedures. Do not
change the logic or settings except for those in Step 1 and subsequent.
Step 1: De-energize IN1 and verify that VO1 goes TRUE and closes OUT1 when SG1 becomes the
active setting group.
Step 2: Transmit the select and operate commands in Table 13-99 to the relay.
Table 13-99. Manual Setting Group Control Selection
Command
Purpose
A=
Gains write access.
CS-143=0
Selects 143 for FALSE operation.
CO-143=0
Executes 143 FALSE operation.
CS-43=1
Selects 43 for TRUE operation.
CO-43=1
Executes 43 TRUE operation.
CS-43=0
Selects 43 for FALSE operation.
CO-43=0
Executes 43 FALSE operation.
EXIT
Exit select and operate mode.
Step 3: Use the RS-LGC command to retrieve logic variable data from the SER. Verify that the setting
group change actions were logged.
Manual Change - Mode 2
Manual Change Mode 2 test procedures are a continuation of the Mode 1 test procedures. Do not change
the logic or settings except for those in Step 1 and subsequent.
Step 1: Transmit the commands in Table 13-100 to the relay. These commands set up the relay for
binary setting group control selection.
Table 13-100. Binary Group Control Selection Setup
Command
Purpose
A=
Gains write access.
SL-GROUP=2,43,0,143
Configures the setting group control function as binary coded selection.
D0 logic = 43, D1 logic = 0, Auto logic = 143
SL-43=2
Sets 43 to On/Off mode.
EXIT;Y
Exit and save settings.
Step 2: Transmit the select and operate commands in Table 13-101 to the relay. For more information
on setting group selection, see Section 4, Protection and Control, Setting Groups.
Table 13-101. Binary Group control Select and Operate Commands
Command
Purpose
A=
Gains write access.
CS-43=0
Selects 43 for FALSE operation.
CO-43=0
Executes 43 FALSE operation.
EXIT
Exit select and operate mode.
Step 3: Verify that VO1 goes FALSE and opens OUT1 when SG0 becomes the active setting group.
9376700990 Rev M
BE1-700 Testing and Maintenance
13-55